Installation and Operation Guide SOLECTRIA XGI 1000
DOCR-070733-F (2/22/2021)
Page 44 of 78
INV 50
INV 49
INV 2
INV 1, Gateway
Inverter
Modem or
Internet
Gateway
Internet
Firewall
Other
Device
Other
Device
Cluster LAN
- XGI Inverters Only -
LAN
- All other Ethernet devices -
Figure 3-26 Networking with Other Devices
Monitoring Compatibility
The SOLECTRIA XGI is compatible with SolrenView and third-party Data Acquisition Systems (DAS). When using
SolrenView monitoring no additional hardware is required. When connecting with third-party monitoring providers,
Ethernet connections must be used; RS485 is not supported.
When integrating SOLECTRIA XGI inverters with third-party monitoring platforms, one of the following methods MUST
be employed in order for the third-party DAS to reach each inverter as an Endpoint Device; 1. Port forwarding, 2. Static
Routing (discussed in detail in Section 3.5.7.) Be sure to consult with the monitoring provider before installation.
Third-Party Data Acquisition System (DAS) Connection
NOTICE !
Ethernet Only Connection: The XGI 1000 series inverter only supports Ethernet connections to a third-party DAS.
Connect the third-party DAS to the onsite LAN, outside of the Cluster LAN(s). Connecting a third-party DAS inside the
Cluster LAN will block communication to the DAS outside of the Cluster LAN.
If DHCP is not enabled on the LAN, a static IP assignment for the GUI must be configured. When using DHCP consider
using a reserved DHCP address.
To allow a third-party DAS (or any other device) to access inverters within a cluster(s) and treat all inverters as Endpoint
Devices, Port Forwarding or Static Routing must be used.