Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
DOCR-071030-A (10/7/2022)
Page 95 of 131
PVSLOWSTARTPWDEL
TA (%)
The output power
should be slow
increased due to the
change of PV
illumination at the
Rule21 standard.
0.01
5.00
10.00
0.01
5.00
10.00
FAULTPOWERT (°C)
The trigger
temperature of
module
95.0
95.0
95.0
95.0
95.0
95.0
FAULTENVT (°C)
The trigger
temperature of
environment
83.0
83.0
83.0
83.0
83.0
83.0
GFCISTATICVALUE
(mA)
The static threshold
value of Leakage
current
100
650
1000
100
650
1000
GFCISTATICT (S)
GFCI static protection
time
0.00
0.20
655.00
0.00
0.20
655.00
GFCIDYNPROFACTOR
GFCI dynamic
protection factor
0.0
100.0
200.0
0.0
100.0
200.0
DCIPROTECTION1
Maximum DCI value1
0.1
0.5
5.0
0.1
0.5
5.0
DCIPROTECTIONT1 (S)
Trip time 1 of DCI
value
0.00
60.00
120.00
0.00
60.00
120.00
DCIPROTECTION2 (mA)
maximum DCI value2
5
950
5000
5
950
5000
DCIPROTECTIONT2 (S)
Trip time 2 of DCI
value
0.00
1.00
120.00
0.00
1.00
120.00
PVSTARTUPVOLT (V)
PV start-up voltage
300
330
400
300
330
400
MPPTSCANPERIOD (S)
MPPTScan Cycle
300
3600
5400
300
3600
5400
ISOPROTECTION (K
Ω)
Minimum insulation
resistance
1
100
2000
1
100
2000
STARUPMINT EMP (°C)
The minimum startup
temperature
-35.0
-30.0
-20.0
-35.0
-30.0
-20.0
DUPLICATION GROUP
Parameter of
repetitive
0
0
100
0
0
100
CTRPARAGROUP
The enabled control
parameters group
0
4
4
0
4
4
PID CHECK SETTING *
PID Checking
enable/disable control
0
0
1
0
0
1
ISLAND PROTECT
Island enable/disable
control 0: Disable
1: Enable
0
1
1
0
1
1
FAN DETECT
Fan detection
enable/disable control
0: Disable 1: Enable
0
1
1
0
1
1
PID BOX *
Pid-box enable or
disable
0
0
1
0
0
1