Table 6-3 Grid Recovery
GRID RECOVERY
SETTING RANGE
IEEE1547
RULE 21
PARAMETER
NAME
DESCRIPTION
MIN
DEFAULT
MAX
MIN
DEFAULT
MAX
VOLTMAX(%)
Recovery Max
threshold of grid
voltage
protection
80.00
108.00
135.00
80.00
108.00
135.00
VOLTMIN (%)
Recovery Min
threshold. grid
voltage
protection
20.00
90.08
100.00
20.00
90.00
100.00
VOLRECOVERYT(S)
Recovery time of
grid voltage
protection
0.00
300.00
655.00
0.00
300.00
655.00
FRQMAX (HZ)
Recovery Max
threshold grid
Frequency
protection
54.00
60.30
66.00
54.00
60.40
66.00
FRQMIN (HZ)
Recovery Min
threshold. grid
Frequency
protection
54.00
59.80
60.00
54.00
58.60
60.00
FRQRECOVERYT(S)
Recovery time of
grid frequency
protection
0.00
300.00
655.00
0.00
300.00
655.00
Table 6-4 Grid Voltage Moving Average
GRID VOLTAGE
MOVING AVERAGE
SETTING RANGE
IEEE1547
RULE21
PARAMETER
NAME
DESCRIPTION
MIN
DEFAULT
MAX
MIN
DEFAULT MAX
VOLTMAX(%)
The upper limit
grid voltage of
100.00
110.00
135.00
100.00
110.00
135.00