Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
DOCR-071030-A (10/7/2022)
Page 78 of 131
IEEE 1547
RULE 21
PARAMETER NAME
DESCRIPTION
MIN
DEFAULT
MAX
MIN
DEFAULT
MAX
GRIDVOLTMAX1(%)
Level 1 Max.
grid voltage
100.00
110.00
135.00
100.00
110.00
135.00
VOLTMAXTRIPTIME1(S)
Level 1 Max.
grid trip
voltage
0.00
1.00
655.00
0.00
12.50
655.00
GRIDVOLTMAX2(%)
Level 2 Max.
grid voltage
100.00
120.00
135.00
100.00
120.00
135.00
VOLTMAXTRIPTIME2(S)
Level 2 Max.
grid trip
voltage
0.00
0.16
655.00
0.00
0.16
655.00
GRIDVOLTMAX3(%)
Level 3 Max.
grid voltage
100.00
120.00
135.00
100.00
120.00
135.00
VOLTMAXTRIPTIME3(S)
Level 3 Max.
grid trip
voltage
0.00
0.16
655.00
0.00
0.16
655.00
GRIDVOLTMIN1 (%)
Level 1 Min.
Grid voltage
30.00
88.00
100.00
30.00
88.00
100.00
VOLTMINTRIPTIME1(S)
Level 1 Min.
grid trip
voltage
0.00
2.00
655.00
0.00
20.50
655.00
GRIDVOLTMIN2 (%)
Level 2 Min.
Grid voltage
30.00
60.00
100.00
30.00
70.00
100.00
VOLTMINTRIPTIME2(S)
Level 2 Min.
grid trip
voltage
0.00
1.00
655.00
0.00
10.50
655.00
GRIDVOLTMIN3(%)
Level 3 Min.
Grid voltage
30.00
45.00
100.00
30.00
50.00
100.00
VOLTMINTRIPTIME3(S)
Level 3 Min.
grid trip
voltage
0.00
0.16
655.00
0.00
0.15
655.00
Table 6-2 Grid Frequency Protection
GRID FREQUENCY PROTECTION
SETTING RANGE
IEEE 1547
RULE 21