Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
DOCR-071030-A (10/7/2022)
Page 121 of 131
MODEL NAME
PVI 25TL-208
PVI 50TL-480
PVI 60TL-480
SYSTEM
TOPOLOGY
Transformerless
MAX. EFFICIENCY
97.0%
98.8%
CEC EFFICIENCY
96.5%
98.5%
STAND-BY / NIGHT
CONSUMPTION
<3W
ENVIRONMENT
ENCLOSURE PROTECTION
DEGREE
NEMA Type 4X
COOLING METHOD
Variable speed cooling fans
OPERATING TEMPERATURE
RANGE
-22°F to +140°F / - 30°C to +60°C
(derating from +113°F / +45°C)
NON-OPERATING
TEMPERATURE RANGE
No low temp minimum to +158°F / +70°C maximum
OPERATING HUMIDITY
0-100%
OPERATING ALTITUDE
13,123.4ft / 4000m (derating from 9842.5ft / 3000m)
AUDIBLE NOISE EMISSION
<60dBA @ 1m and 25°C
DISPLAY AND COMMUNICATION
USER INTERFACE AND DISPLAY
LED, LCD
INVERTER MONITORING
SunSpec, Modbus RS485
SITE LEVEL MONITORING
Ethernet Network Card (1 per 32 inverters)
MODBUS DATA MAPPING
Solectria Proprietary, Complies with SunSpec Modbus
REMOTE DIAGNOSTICS / FW
UPGRADE FUNCTIONS
Standard / with Ethernet Network Card
MECHANICAL DATA
DIMENSIONS (WXHXD)
39.4 x 23.6 x 10.24 in. (600×1000×260mm)
WEIGHT
Inverter: 123.5 lbs (56kg); Wire-box: 33 lbs (15kg)
MOUNTING / INSTALLATION
ANGLE
15
°
to 90° from horizontal. 75° and below: shade cover required
AC TERMINATION
M8 Stud Type Terminal Block (Wire range: #6-3/0AWG Cu/Al)
Lugs not supplied
DC TERMINATION
Screw Clamp, Neg. Busbar (RSD version) Wire range: #14 - #6AWG CU
FUSED STRING INPUTS (5 PER
MPPT)
20A standard fuse value (Fuse values up to 30A acceptable)
SAFETY
PV ARC-FAULT CIRCUIT
PROTECTION
Type 1
SAFETY AND EMC STANDARD
UL 1741-SB, UL 1741SA-2016, UL1699B, UL1998, CSA-C22.2 No. 107.1-01,
FCC Part 15 (Subpart B, Class A)
GRID STANDARD AND SRD
IEEE1547a-2014 / IEEE 1547-2018 (depending on firmware), Rule 21, ISO-NE
SMART-GRID FEATURES
Volt-RideThru, Freq-RideThru, Ramp-Rate, Specified-PF, Volt-VAr, Freq-
Watt, Volt-Watt, Watt-VAr