Installation and Operation Guide SOLECTRIA® PVI 25TL-208, PVI 50TL-480 and PVI 60TL-480
DOCR-071030-A (10/7/2022)
Page 89 of 131
ReactivePowerDerating
The
R
EACTIVE
P
OWER
D
ERATING
submenu is used to set the Grid reactive power derating parameters including PF
parameters and Q parameters, etc. The parameters are shown in Table 6-10. Press
ENT
to start the modes after
the parameters are set.
INFO
✔
The PF and Q value can be adjusted by remote software if the “Remote” is selected. Remote can be selected
thru the Modbus map and the appropriate register.
PF vs Grid Voltage
PFCurveP1
P1/4
PFpCurvePF1
100.0%
1.000
50.0%
PFpCurvePF2
PFCurveP2
PFCurveTriVolt
PFCurveUndoVolt
-0.900
100.00%
90.00%
QuCurveQ2i
P3/4
5.0%
20.0%
50.0%
QuCurveTriPower
QuCurveUndoPower
Reactive Power vs Grid Voltage
Grid Reactive Power Derating
P4/4
CtrMode
0
Percentage
0.0%
Reactive Power vs Grid Voltage
QuCurveQ1
QuCurveU1
P2/4
-50.0%
110.00%
0.0%
107.99%
92.01%
0.0%
90.00%
QuCurveU2
QuCurveQ2
QuCurveU1i
QuCurveQ1i
QuCurveU2i
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Control Command
PFSetValue
1.000
ReactivePowerOver
Disable
Figure 6-12 ReactivePowerDerating Parameter Screens PVI 25TL-480
PF vs Grid Voltage
PFCurveP1
P1/4
PFpCurvePF1
100.0%
1.000
50.0%
PFpCurvePF2
PFCurveP2
PFCurveTriVolt
PFCurveUndoVolt
-0.900
100.00%
90.00%
QuCurveQ2i
P3/4
5.0%
20.0%
50.0%
QuCurveTriPower
QuCurveUndoPower
Reactive Power vs Grid Voltage
Grid Reactive Power Derating
P4/4
CtrMode
0
Percentage
0.0%
Reactive Power vs Grid Voltage
QuCurveQ1
QuCurveU1
P2/4
-50.0%
110.00%
0.0%
107.99%
92.01%
0.0%
90.00%
QuCurveU2
QuCurveQ2
QuCurveU1i
QuCurveQ1i
QuCurveU2i
LVRT/HVRT Setup
Setting
P1/2
System Parameters
Protection Parameters
Power Derating Setup
Reactive Power Derating Setup
ARC Parameters
Control Command
PFSetValue
1.000
Reserve
Figure 6-13 ReactivePowerDerating Parameter Screens PVI 50/60TL-480
(1)
PF Set
: Set the PF value. This function changes the reactive power by adjusting the Power Factor.
NOTE
:
Change the reactive power by adjusting the PowerFactor.
(2)
PF(P) Curve:
Use this mode to follow the default or user-specified PF curve.
NOTE
: The power factor
changes according to the power change, as shown in Figure 6-14.