Chapter 7: Using the Digital Operator
7-29
Using the Panel Operator
1. Input the (intended) 0V reference voltage from the host controller or external cir-
cuit.
2. Press the MODE/SET key to select the auxiliary function mode.
3. Press the Up Arrow
or Down Arrow key to select the parameter Fn009.
4. Press the DATA/SHIFT key for a minimum of one second, and the display will
be as shown below.
5. Press the MODE/SET key, and the following display will flash for one second.
The reference offset will be automatically adjusted.
6. Press the DATA/SHIFT key for a minimum of one second to return to the auxil-
iary function mode display.
This completes the speed/torque reference offset automatic adjustment.