Sigma II User’s Manual
Chapter 5: Parameter Settings and Functions
5-50
5.3.3
Input Circuit Signal Allocation
The functions allocated to sequence input signal circuits can be changed. CN1 con-
nector input signals are allocated with the default settings as shown in the following
table.
Note:
*
The functions of these input signals are automatically switched according to the setting at parameter Pn000.1
as long as Pn50A.0 is set to 0.
The following parameter is used to enable input signal allocation.
Note: The default setting for parameter Pn50A.0 is 0. Functions and applications in this manual are gener-
CN1
Connector
Terminal
Numbers
Input Terminal
Name
Default Setting
Symbol
Name
40
SI0
/S-ON
Servo ON
41
SI1
/P-CON
(Proportional control refer-
ence) *
42
SI2
P-OT
Forward run prohibit
43
SI3
N-OT
Reverse run prohibit
44
SI4
/ALM-RST
Alarm reset
45
SI5
/P-CL
(Forward current limit) *
46
SI6
/N-CL
(Reverse current limit) *
Parameter
Signal
Setting
Description
Pn50A.0
Input Signal Allocation Mode
Default Setting: 0
Speed/Torque Control,
Position Control
Pn50A.0 Setting
Description
0
Default setting for sequence input signal allocation.
This setting is the same as Yaskawa SGDB-
o
AD
o
servo amplifiers.
1
Enables any sequence input signal settings.
SGDH-
MODE/SET
DATA/
CHARGE
POWER
SERVOPACK
200V