YASKAWA
SIEP C730600 86F MECHATROLINK-II Technical Manual
33
Bit
Item
Remarks
4
•
YASKAWA AC Drive 1000-Series
Drive terminal output
Bit0: Terminal M1-M2
Bit1: Terminal P1-PC
Bit2: Terminal P2-PC
•
YASKAWA AC Drive GA500
Drive terminal output
Bit0: Terminal MA/MB-MC
Bit1: Terminal P1-C1
Bit2: Terminal P2-C2
•
YASKAWA AC Drive GA700, GA800, CR700, and CH700
Drive terminal output
Bit0: Multi-function digital output 1 (M1-M2)
Bit1: Multi-function digital output 2
Bit2: Multi-function digital output 3
Bit3: Multi-function digital output 4
Bit4: Multi-function digital output 5
•
YASKAWA AC Drive 1000-Series
Terminal M1-M2 (Enabled when
H2-01 = F
)
Terminal P1-PC (Enable when
H2-02 = F
)
Terminal P2-PC (Enable when
H2-03 = F
)
•
YASKAWA AC Drive GA500
Drive terminal output
Terminal MA/MB-MC (Enabled when
H2-01 = F
)
Terminal P1-C1 (Enabled when
H2-02 = F
)
Terminal P2-C2 (Enabled when
H2-03 = F
)
•
YASKAWA AC Drive GA700, GA800, CR700, and CH700
Multi-function digital output 1 (Enable when
H2-01 = F
)
Multi-function digital output 2 (Enable when
H2-02 = F
)
Multi-function digital output 3 (Enable when
H2-03 = F
)
Multi-function digital output 4 (Enable when
H2-04 = F
)
Multi-function digital output 5 (Enable when
H2-05 = F
)
5
PID target
Drive: 0.01%
6
Pulse train output
Drive: 1 Hz
7
V/f gain
-
8
Reserved
-
9
Command selection
Bit1: PID target value enable
-
A - F
Not used
-
*1
Terminals are different for different drive models.
•
YASKAWA AC Drive 1000-Series
CIMR-xAx, CIMR-xTx, CIMR-xKx, CIMR-xBx, CIMR-xDx: P1-PC
CIMR-xUx, CIMR-xCx: M3-M4
•
YASKAWA AC Drive GA700, GA800
CIPR-GAxAx, CIPR-GAxTx, CIPR-GAxUx, CIPR-GAxCx, CIPR-GAxBx, CIPR-GAxKx, CIPR-GAxDx: M3-M4
•
YASKAWA AC Drive CR700, CH700
CIPR-CR70Ax, CIPR-CR70Tx, CIPR-CH70Bx: M3-M4
*2
Terminals are different for different drive models.
•
YASKAWA AC Drive 1000-Series
CIMR-xAx, CIMR-xTx, CIMR-xKx, CIMR-xBx, CIMR-xDx: P2-PC
CIMR-xUx, CIMR-xCx: M5-M6
•
YASKAWA AC Drive GA700, GA800
CIPR-GAxAx, CIPR-GAxTx: P1-C1
CIPR-GAxUx, CIPR-GAxCx, CIPR-GAxBx, CIPR-GAxKx, CIPR-GAxDx: M5-M6
•
YASKAWA AC Drive CR700, CH700
CIPR-CR70Ax, CIPR-CR70Tx, CIPR-CH70Bx: M5-M6
*3
Available in CIPR-GA70Ax, CIPR-GA70Tx, CIPR-CR70x, CIPR-CH70x
•
YASKAWA AC Drive GA700
CIPR-GA70Ax, CIPR-GA70Tx: P2-C2
•
YASKAWA AC Drive CR700, CH700
CIPR-CR70Ax, CIPR-CR70Tx, CIPR-CH70Bx: P1-C1
*4
Available in CIPR-CR70x, CIPR-CH70x
•
YASKAWA AC Drive CR700, CH700
CIPR-CR70Ax, CIPR-CR70Tx, CIPR-CH70Bx: P2-C2
Table 8.12 SEL MON1/2 (3/4, 5/6) Selection Range
MON1/2
Item
Remarks
0
Nothing Selected
-
1
Motor Speed
Same as
U1-05
, determined by
o1-03
2
Torque Reference (Monitor)
Same as
U1-09
, 0.1%
3
Speed Detection PG 1 Counter
-
4
Frequency Reference
Same as
U1-01
, determined by
o1-03
5
Analog Input Terminal A2
Same as
U1-14
, 0.1%
6
Main circuit current voltage
Same as
U1-07
, 1 V
7
Drive alarm
Refer to
8
Drive warning
Refer to
9
Multi-Function Output Terminal Status
Same as
U1-11
A
Analog Input Terminal A3
Same as
U1-15
, 0.1%