SIEP C730600 86F MECHATROLINK-II Technical Manual
Table 9.4 Reception Failures in Each Phase
Communication Phase
Communications Failure
Transmission Cycle
First
Second (Consecutive)
Fault
Phase 1
-
-
-
Phase 2
96
E6
E6
Phase 3
96
E6
E6
Table 9.5 Alarm Code (MECHATROLINK-II Response ALARM Value)
ALARM
Description
Fault Type
96
MECHATROLINK-II communications fault warning
Communications warning
E5
MECHATROLINK-II WDT Error
Communications alarm
E6
MECHATROLINK-II communications fault
Communications alarm
Table 9.6 Fault Types
Fault
Description
Communications failure
Transmission LSI detected a data reception failure.
Transmission cycle fault
A timing fault of a synchronous frame in a transmission cycle was detected.
Watchdog timer error
A WDT count fault in a synchronous frame was detected.
■
Other Faults
The following table shows other faults that can be detected by the SI-T3. If a warning occurs, operation will
follow the previous command.
Table 9.7 Other fault detected by SI-T3
ALARM
Description
Fault Type
Operation when Fault Occurs
94
Data setting warning
Communications warning
Received commands are ignored.
95
Command warning
Communications warning
Received commands are ignored.
EC
WDC fault with drive
Communications alarm
Waits for power supply to be reset.
ED
Drive access permission fault (Access not possible 10 consecutive
times)
Communications alarm
Waits for power supply to be reset.
EE
Drive monitor timer over (1 s elapsed)
Communications alarm
Waits for power supply to be reset.
Received commands are ignored.
*1
If the ERR indicator is not lit or flashing, any commands that are received will be ignored.
◆
Drive Fault Notification
If a fault is detected in the drive, SI-T3 stores the alarm or warning code in the MECHATROLINK-II ALARM
command and simultaneously activates the relevant bit in the STATUS field.
and
show the alarm codes for SI-T3 notification if a fault is detected in the drive.
Table 9.8 Drive Alarm Codes
ALRM Code (Hex.)
Keypad Display
Description
00
SCF
Safety Circuit Fault
Note:
When using YASKAWA AC Drive 1000-Series,
“
SCF
”
(Safety Circuit Fault) will not be displayed.
02
Uv1
DC Bus Undervoltage
03
Uv2
Control Power Undervoltage
04
Uv3
Soft Charge Answerback Fault
06
GF
Ground Fault
07
oC
Overcurrent
08
ov
Overvoltage
09
oH
Heatsink Overheat
0A
oH1
Heatsink Overheat
0B
oL1
Motor Overload