5 Installation Procedure
19
YASKAWA
SIEP YEACOM 06 V1000 Option PROFINET SI-EP3/V Technical Manual
12.
Attach the option to the drive. Properly seat the tabs on the left and right sides of the option to the drive case.
Figure 16
Figure 16 Connect the Option
13.
Connect the ground wire at the option ground terminal. Tighten the screw to 0.5 ~ 0.6 Nm or (4.4 ~ 5.3 in lbs)
using an M3 Phillips screwdriver.
Figure 17
Figure 17 Connect the Ground Wire to the Option
14.
To connect the option to a network, firmly connect RJ45 8-pin Shielded Twisted Pair Cat 5e cable(s) into the
modular connector ports.
Note:
Do not connect or disconnect the communication cable while the drive is powered up or while the drive is in operation. Failure to
comply may cause a static discharge, which will cause the option card to stop working properly. Cycle power on the drive and
option card to reestablish functionality.
Figure 18
Figure 18 Communication Cable Ports
Line up tabs
Line up tabs
Option ground
terminal