3 Wiring and Connection
3.1.2 Using a Standard Power Supply Input (Single-phase 100-V, Three-phase 200-V, or Three-phase 400-V)
3-10
(5) Molded-case Circuit Breaker and Fuse Capacities
The following table describes the molded-case circuit breaker and fuse capacities of the SERVOPACK.
Note 1. To comply with the low voltage directive, connect a fuse to the input side. Select the fuse or molded-case circuit
breaker for the input side from among models that are compliant with UL standards.
The table above also provides the net values of current capacity and inrush current. Select a fuse and a molded-
case circuit breaker which meet the breaking characteristics shown below.
• Main circuit, control circuit: No breaking at three-times the current values of the table for 5 s.
• Inrush current: No breaking at the same current values of the table for 20 ms.
2. In accordance with UL standards, the following restrictions apply.
Main Circuit
Power
Supply
Maximum
Applicable
Motor
Capacity
[kW]
SERVOPACK
Model
SGDV-
Power Supply
Capacity per
SERVOPACK
[kVA]
Current Capacity
Inrush Current
Main Circuit
[Arms]
Control
Circuit
[Arms]
Main
Circuit
[A0-p]
Control
Circuit
[A0-p]
Single-phase,
100-V
0.05 R70F
0.2
1.5
0.38
16.5
35
0.1 R90F
0.3
2.5
0.2 2R1F
0.7
5
0.4 2R8F
1.4
10
Three-phase,
200-V
0.05 R70A
0.2
1.0
0.2
33
70
0.1 R90A
0.3
1.0
0.2 1R6A
0.6
2.0
0.4 2R8A
1
3.0
0.5
3R8A
1.4
3.0
33
0.75 5R5A
1.6
6.0
1.0
7R6A
2.3
6.0
1.5
120A
3.2
7.3
0.25
2.0
180A
4
9.7
3.0
200A
5.9
15
5.0
330A
7.5
25
0.3
65.5
7.5
550A
14.6
37
Three-phase,
400-V
0.5
1R9D
1.1
1.4
1.2
17
–
1.0
3R5D
2.3
2.9
1.5
5R4D
3.5
4.3
2.0
8R4D
4.5
5.8
1.4
34
3.0
120D
7.1
8.6
5.0
170D
11.7
14.5
57
7.5
260D
14.4
21.7
1.5
34
SERVOPACK
Model SGDV-
Restrictions
180A, 200A
Available rated current for molded-case circuit breaker: 40 A or less
330A
• Available rated current for non-time delay fuse: 70 A or less
• Available rated current for time delay fuse: 40 A or less
• Do not use single wires.
550A
• Available rated current for molded-case circuit breaker: 60 A or less
• Available rated current for non-time delay fuse or time delay fuse: 60 A or
less
260D
• Available rated current for molded-case circuit breaker: 60 A or less
• Available rated current for non-time delay fuse: 60 A or less
• Available rated current for time delay fuse: 35 A or less