4 Operation
4.4.1 Internal Force Limit
4-30
4.4
Limiting Force
The SERVOPACK provides the following three methods for limiting output force to protect the machine.
4.4.1
Internal Force Limit
This function always limits maximum output force by setting values of following parameters.
The setting unit is a percentage of the motor rated force.
Note 1. Too small a force limit setting will result in insufficient force during acceleration and deceleration.
2. The maximum force of the linear servomotor is used whenever the value exceeds the maximum force is set.
Trace Waveform of S
Note: The waveform reverses in case of analog monitor (CN5) output.
Limiting Method
Description
Reference
Section
Internal force limit
Always limits force by setting the parameter.
4.4.1
External force limit
Limits force by input signal from the host controller.
4.4.2
Force limit with Command
Option Module
Limits force by inputting a desired force limit command to the
Command Option Module from the host controller.
Refer to the manual
of the connected
Command Option
Module.
Pn483
Forward Force Limit
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
0 to 800
1%
800
Immediately
Setup
Pn484
Reverse Force Limit
Classification
Setting Range
Setting Unit
Factory Setting
When Enabled
0 to 800
1%
800
Immediately
Setup
Speed
Position
Force
Speed
Position
Force
Speed
Maximum force
t
Speed
Pn484
Pn483
Limiting force
t
No Internal Force Limit
(Maximum Force Can Be Output)
Internal Force Limit