7-19
Registers
Drive Parameter Registers continued (Read/Write)
REGISTER
PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION
SETTING
VALUE
13Dh
n061
Fault Contact Selection
0
Closed during auto. restart
0
at Auto Restart
1
Open during auto. restart
13Eh
n062
Prohibit Frequency 1
0.0 to 400.0 Hz
0
13Fh
n063
Prohibit Frequency 2
0.0 to 400.0 Hz
0
140h
n064
Prohibit Frequency Deadband
0.0 to 25.5 Hz
1.0
141h
n065
Elapsed Timer Selection
0
Accumulated time during power on
1
1
Accumulated time during running
142h
n066
Elapsed Timer 1
0 to 9999 hours
0
143h
n067
Elapsed Timer 2
0 to 27 (x 10,000 hours)
0
144h
n068
DC Injection Current
0 to 100% (100%=drive rated current)
50
145h
n069
DC Injection Time at Stop
0.0 to 10.0 seconds
0.0
146h
n070
DC Injection Time at Start
0.0 to 10.0 seconds
0.0
147h
n071
Torque Compensation Gain
0.0 to 3.0
1.0
148h
n072
Stall Prevention during Decel
0
Disabled
1
1
Enabled
149h
n073
Stall Prevention Level during Accel
30 to 200% (@200% disabled during Accel)
(1)
14Ah
n074
Stall Prevention Level at Set Freq.
30 to 200% (@200% disabled during running)
(1)
14Bh
n075
Speed Coincide Frequency
0.0 to 400.0 Hz
0.0
14Ch
n076
Frequency Agreed Detect. Width
0.0 to 25.5 Hz
2.0
14Dh
n077
Overtorque/ Undertorque Detection
(OL3)
0
Detection disabled
1
Overtorque detect only at set
frequency; operation continues
2
Overtorque detect during all frequency
conditions; operation continues
0
3
Overtorque detect only at set
frequency; coast to stop
Notes:
1. Initial value depends on GPD 506 capacity.
Содержание GPD 506/P5
Страница 1: ...GPD 506 Modbus RTU Technical Manual...
Страница 10: ...RS 232 C D Serial Communication 2 3 pin out for devices other than a computer PC such as a PLC may vary...
Страница 47: ...7 13 Registers 29 Up Down Command 1...
Страница 49: ...7 15 Registers 15 Closed by Serial Communications 16 PID Feedback Loss...
Страница 51: ...7 17 Registers 7 to 9 asynchronous...
Страница 60: ...Error Codes and Troubleshooting 8 3...