7-22
Registers
Drive Parameter Registers continued (Read/Write)
167h
n103
Modbus Frequency Reference
0
0.1 Hz/ 1
0
Unit
1
0.01 Hz/ 1
2
100%/ 30000
3
0.01%/ 1
168h
n104
Modbus Slave Address
0 to 31
1
169h
n105
Modbus Baud Rate Selection
0
2400 bps
2
1
4800 bps
2
9600 bps
16Ah
n106
Modbus Parity Selection
0
No parity
1
Even parity
0
2
Odd parity
16Bh
n107
Slip Compensation Gain
0.0 to 9.9%
0.0
16Ch
n108
No-load motor current
0 to 99%
30
16Dh
n109
Slip Comp. Primary Delay
Time Constant
0.0 to 25.5 seconds
2.0
16Eh
n110
Operator Connection Fault Detection
Selection
0
Cycle Stop
0
1
Immediate
16Fh
n111
Local/ Remote Changeover
Fault Detection Selection
0
Disabled
0
1
Enabled
170h
n112
Low frequency
OL start point
0.0 to 6.0 Hz
6.0
171h
n113
Continuous operation
level at 0.0 Hz
25 to 100%
50
172h
n114
Square Root N Monitor Gain
0 to 99
0
173h
n115
KVA selection
00-35
(1)
174h
n116
CT/ VT Selection
0
Constant Torque
(1)
1
Variable Torque
Notes:
1. Initial value depends on GPD 506 capacity.
Содержание GPD 506/P5
Страница 1: ...GPD 506 Modbus RTU Technical Manual...
Страница 10: ...RS 232 C D Serial Communication 2 3 pin out for devices other than a computer PC such as a PLC may vary...
Страница 47: ...7 13 Registers 29 Up Down Command 1...
Страница 49: ...7 15 Registers 15 Closed by Serial Communications 16 PID Feedback Loss...
Страница 51: ...7 17 Registers 7 to 9 asynchronous...
Страница 60: ...Error Codes and Troubleshooting 8 3...