7-5
Registers
Monitor Registers (continued)
REGISTER
FUNCTION
BIT
DATA
DESCRIPTION
(in hex)
NO.
SET
022h
Communication Data Link Status
0
1
Write in Progress
1
.not used
2
not used
3
1
Upper/Lower Fault
4
1
Consistency Fault
5
not used
6
not used
7
not used
8
not used
9-15
will return zeros
023h
Frequency Reference
0-15
units depend on constant n105
(1)
024h
Output Frequency
0-15
units depend on constant n105
(1)
025h
Not Used
will return zeros
026h
Not Used
will return zeros
027h
Output Current
0-15
(1 Amp/10)
(2)
028h
Output Motor Voltage
0-15
(1 Volt/1)
029h
Reserved
0-15
02Ah
Reserved
0-15
02Bh
External Terminal Input Value
0
1
Input terminal S1 is closed
1
1
Input terminal S2 is closed
2
1
Input terminal S3 is closed
3
1
Input terminal S4 is closed
4
1
Input terminal S5 is closed
5
1
Input terminal S6 is closed
6
1
not used
7
1
not used
Notes:
1. Frequency Reference unit (n103) default setting is ‘0’ (0.1Hz / 1).
2. Value in register divided by 10 equals actual amps.
Содержание GPD 506/P5
Страница 1: ...GPD 506 Modbus RTU Technical Manual...
Страница 10: ...RS 232 C D Serial Communication 2 3 pin out for devices other than a computer PC such as a PLC may vary...
Страница 47: ...7 13 Registers 29 Up Down Command 1...
Страница 49: ...7 15 Registers 15 Closed by Serial Communications 16 PID Feedback Loss...
Страница 51: ...7 17 Registers 7 to 9 asynchronous...
Страница 60: ...Error Codes and Troubleshooting 8 3...