7-8
Registers
Drive Parameter Registers (Read/Write)
REGISTER
PARAMETER
PARAMETER
PARAMETER
LIMITS / DESCRIPTION
INITIAL
(in hex)
FUNCTION
SETTING
VALUE
101h
n001
Parameter Selection /
0
n001 read & set; n002-n116 read only
Initialization
1
n001-n035 read & set;
n036-n116 read only
2
n001-n053 read & set;
1
n054-n116 read only
3
n001-n116 read & set
8
initialize for 2-wire control
9
initialize for 3-wire control
102h
n002
Operation Mode Selection
Run Command
Frequency Ref.
0
Operator
Operator
1
External Terminals
Operator
2
Operator
External Terminals
3
External Terminals
External Terminals
4
Operator
Serial Comm.
3
5
External Terminals
Serial Comm.
6
Serial Comm.
Serial Comm.
7
Serial Comm.
Operator
8
Serial Comm.
External Terminals
103h
n003
Input Voltage
150.0-255.0 Volts (230V drive)
230.0
150.0-510.0 Volts (460V drive)
460.0
104h
n004
Stop Method
0
Ramp to stop
1
Coast to stop
0
2
Coast to stop (Timer 1)
3
Coast to stop (Timer 2)
105h
n005
Power Rotation
0
Counter clockwise
0
1
Clockwise
Содержание GPD 506/P5
Страница 1: ...GPD 506 Modbus RTU Technical Manual...
Страница 10: ...RS 232 C D Serial Communication 2 3 pin out for devices other than a computer PC such as a PLC may vary...
Страница 47: ...7 13 Registers 29 Up Down Command 1...
Страница 49: ...7 15 Registers 15 Closed by Serial Communications 16 PID Feedback Loss...
Страница 51: ...7 17 Registers 7 to 9 asynchronous...
Страница 60: ...Error Codes and Troubleshooting 8 3...