6-8 The Message Format
Write Multiple Registers - 10h
The multiple register write function (10h) allows the master to write data to the drive’s registers. The
multiple register write message format is shown below.
Command Message
Each GPD 506’s slave address is set in advance by the drive parameter n104. Valid slave
addresses must be in the range of 1 to 31 decimals (1 to 1F hex). No two slaves may have the
same address. The master addresses the slave by placing the slave address in the address field of
the message. In the command message above, the slave is addressed at 1.
By setting the slave address to zero (0), the master can send operation signals (register 001h) and
frequency reference (register 002h) to all slaves on the network. The master can send a single
transmission to all the slaves simultaneously. This is called simultaneous broadcasting. In a
simultaneous broadcast message all of the slaves on the network act upon one message.
Simultaneous Broadcast registers are shown in Chapter 7, Registers.
The function code of this message is 10h (write multiple registers).
01h
SLAVE ADDRESS
FUNCTION CODE
10h
00h
01h
START-
ING
REGISTER
NO.
UPPER
LOWER
04h
CRC-16
NO. OF DATA BYTES
QTY.
00h
02h
UPPER
LOWER
00h
01h
UPPER
LOWER
DATA TO
NEXT
REGISTER
17h
70h
UPPER
LOWER
DATA TO
FIRST
REGISTER
6Dh
B7h
LOWER
UPPER
The first register, 01h
(Operation Command) has a
value of 01h or 1 dec.
(forward run command)
The next register, 02h
(Frequency Reference) has
a value of 1770h or 6000
dec. (60.00 Hz)
Содержание GPD 506/P5
Страница 1: ...GPD 506 Modbus RTU Technical Manual...
Страница 10: ...RS 232 C D Serial Communication 2 3 pin out for devices other than a computer PC such as a PLC may vary...
Страница 47: ...7 13 Registers 29 Up Down Command 1...
Страница 49: ...7 15 Registers 15 Closed by Serial Communications 16 PID Feedback Loss...
Страница 51: ...7 17 Registers 7 to 9 asynchronous...
Страница 60: ...Error Codes and Troubleshooting 8 3...