1.5 Defaults by Drive Model Selection (o2-04)
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
89
Table 1.6 4.16 kV Class Drives Default Settings by Drive Model Selection
L8-09
Output Ground Fault
Detection Selection
–
1
1
1
1
1
1
1
1
1
1
1
L8-33
FAN Board Use
Selection
–
1
1
1
1
1
2
2
2
2
2
2
L8-87
Transformer Overheat
Alarm (TMA) Level
°
C
130
130
130
130
130
130
130
130
130
130
130
L8-88
Transformer Overheat
Fault (TME) Level
°
C
140
140
140
140
140
140
140
140
140
140
140
n1-03
Hunting Prevention Time
Constant
ms
30
30
30
30
30
30
30
30
30
30
30
n9-02
Output Current
Detection Gain
–
1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000 1.0000
n9-71
Input Current
Conversion Coefficient
–
0.0340 0.0340 0.0235 0.0150 0.0110 0.0094 0.0060 0.0060 0.0040 0.0040 0.0030
o2-11
Reference Voltage for
Input Voltage Detection
V
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
3300
<61> Parameter numbers shown in parenthesis are valid for motor 2.
<62> The alarm detection level differs for each drive model because of the different thermistor position on each drive.
No.
Name
Unit
Default Settings
–
Model
CIMR-
MV2
–
039 052 058 064 077 093 102 115 125 155 190 220 250 285 315 340 375 440 505 575 625
o2-04 Drive Model
Selection
–
54
40
41
42
43
44
45
46
47
48
49
4A
4B
4C
4D
4E
4F
50
51
52
53
E2-11
(E4-11)
Motor Rated
Power
kW
(HP)
300
(402)
300
(402)
330
(442)
370
(496)
440
(590)
540
(724)
590
(791)
660
(885)
720
(965)
890
(1193)
1100
(1475)
1270
(1702)
1440
(1931)
1640
(2198)
1820
(2440)
1960
(2627)
2160
(2895)
2540
(3405)
2910
(3901)
3310
(4436)
3600
(4826)
b3-04
V/f Gain
during Speed
Search
%
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
80
b3-06
Output Current
1 during Speed
Search
–
0.5
0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-11
Speed Search
Method
Switching
Level (Speed
Estimate Type
Speed Search)
%
5.0
5.0 5.0 5.0 5.0 5.0 5.0 5.0 5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
E2-01
(E4-01)
Motor Rated
Current
A
40.0 40.0 50.0 50.0 70.0 80.0 90.0 100.0 110.0 130.0 160.0 190.0 210.0 240.0 270.0 290.0 320.0 370.0 430.0 490.0 530.0
E2-02
(E4-02)
Motor Rated
Slip
Hz
0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25
E2-03
(E4-03)
Motor
No-Load
Current
A
10.0 10.0 13.0 13.0 18.0 20.0 23.0 25.0 28.0 33.0 40.0 48.0 53.0 60.0 68.0 73.0 80.0 93.0 108.0 123.0 133.0
E2-05
(E4-05)
Motor
Line-to-Line
Resistance
W
0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300 0.300
E2-06
(E4-06)
Motor Leakage
Inductance
%
20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
E2-10
(E4-10)
Motor Iron
Loss for
Torque
Compensation
W
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
No.
<61>
Name
Unit
Default Settings
–
Model
CIMR-MV2
–
035
050
070
100
140
200
260
330
400
520
650
o2-04
Drive Model Selection –
20
21
22
23
24
25
26
27
28
29
2A
E2-11 (E4-11) Motor Rated Power
kW
160
230
320
460
640
910
1190
1510
1830
2380
2970
MV1000ParameterGuide_E_conditional.book 89 ページ 2013年10月11日 金曜日 午後8時18分