2.7 H: Terminal Functions
198
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
u
H4: Analog Outputs
These parameters assign functions to analog outputs 1 to 4 for monitoring a specific aspect of drive performance.
n
H4-01, H4-11, H4-21, H4-31: Analog Output 1, 2, 3, 4 Monitor Selections
Sets the desired drive monitor parameter U
-
to output as an analog value via analog outputs 1 to 4. Refer to
for a list of all monitors. The “Analog Output Level” column indicates if a monitor can be used for
analog output.
Example: Enter “103” for U1-03.
A setting of 031 or 000 applies no drive monitor to the analog output. With this setting, terminal functions as well as
analog output levels can be set by a PLC via a communication option card or MEMOBUS/Modbus (through mode).
n
H4-02, H4-03: Analog Output 1 Gain and Bias
H4-12, H4-13: Analog Output 2 Gain and Bias
H4-22, H4-23: Analog Output 3 Gain and Bias
H4-32, H4-33: Analog Output 4 Gain and Bias
Parameter H4-02, H4-12, H4-22, and H4-32 set analog outputs 1 to 4 signal level equal to 100% of the monitor (gain).
Parameter H4-03, H3-13, H3-23, H3-33 set the bias added to the monitor output for analog outputs 1 to 4. Both are set as
a percentage, where 100% equals 10 Vdc analog output. The output voltage of both terminals is limited to 10 Vdc.
The output signal range can be selected between 0 to +10 Vdc or -10 to +10 Vdc using parameter H4-05, H4-15, H4-25,
and H4-35.
illustrates how gain and bias settings work.
No.
Name
Setting Range
Default
H4-01
Analog Output 1 Monitor Selection
000 to 999
102
H4-11
Analog Output 2 Monitor Selection
000 to 999
103
H4-21
Analog Output 3 Monitor Selection
000 to 999
000
H4-31
Analog Output 4 Monitor Selection
000 to 999
000
No.
Name
Setting Range
Default
H4-02
Analog Output 1 Gain
-999.9 to 999.9%
100.0%
H4-03
Analog Output 1 Bias
-999.9 to 999.9%
0.0%
H4-12
Analog Output 2 Gain
-999.9 to 999.9%
100.0%
H4-13
Analog Output 2 Bias
-999.9 to 999.9%
0.0%
H4-22
Analog Output 3 Gain
-999.9 to 999.9%
100.0%
H4-23
Analog Output 3 Bias
-999.9 to 999.9%
0.0%
H4-32
Analog Output 4 Gain
-999.9 to 999.9%
100.0%
H4-33
Analog Output 4 Bias
-999.9 to 999.9%
0.0%
MV1000ParameterGuide_E_conditional.book 198 ページ 2013年10月11日 金曜日 午後8時18分