1.3 Parameter Table
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
45
F5: Contact Output Card (DO-A3)
F5-01
(399H)
Contact Output 1
(Terminal P1-PC)
Output Selection
Sets the function for contact outputs 1 to 8 (terminals P1-PC to P6-PC,
M1-M2, and M3-M4).
Default: 0
Min: 0
Max: 1FF
F5-02
(39AH)
Contact Output 2
(Terminal P2-PC)
Output Selection
Default: 1
Min: 0
Max: 1FF
F5-03
(39BH)
Contact Output 3
(Terminal P3-PC)
Output Selection
Default: 2
Min: 0
Max: 1FF
F5-04
(39CH)
Contact Output 4
(Terminal P4-PC)
Output Selection
Default: 4
Min: 0
Max: 1FF
F5-05
(39DH)
Contact Output 5
(Terminal P5-PC)
Output Selection
Default: 6
Min: 0
Max: 1FF
F5-06
(39EH)
Contact Output 6
(Terminal P6-PC)
Output Selection
Default: 37
Min: 0
Max: 1FF
F5-07
(39FH)
Contact Output 7
(Terminal M1-M2)
Output Selection
Default: F
Min: 0
Max: 1FF
F5-08
(3A0H)
Contact Output 8
(Terminal M3-M4)
Output Selection
Default: F
Min: 0
Max: 1FF
F5-09
(3A1H)
DO-A3 Output
Mode Selection
0: Output terminals are each assigned separate output functions.
1: Binary code output
2: Use output terminal functions selected by parameters F5-01 through
F5-08.
Default: 0
Min: 0
Max: 2
F6: Communication Option Cards
• F6-01 to F6-03 and F6-06 to F6-08 are parameters used for DeviceNet and PROFIBUS-DP. Other parameters in the F6 group are used for
communication-protocol-specific settings.
• For details, refer to the technical manual of each communication option card.
F6-01
(3A2H)
Communications
Error Operation
Selection
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only
Default: 1
Min: 0
Max: 3
F6-02
(3A3H)
External Fault from
Comm. Option
Detection Selection
0: Always detected
1: Detection during run only
Default: 0
Min: 0
Max: 1
F6-03
(3A4H)
External Fault from
Comm. Option
Operation Selection
0: Ramp to stop. Decelerate to stop using the deceleration time in C1-02.
1: Coast to stop
2: Fast Stop. Decelerate to stop using the deceleration time in C1-09.
3: Alarm only
Default: 1
Min: 0
Max: 3
F6-04
(3A5H)
bUS Error Detection
Time
Sets the delay time for error detection if a bus error (Option Communication
Error) occurs.
Default: 2.0 s
Min: 0.0 s
Max: 5.0 s
–
F6-06
(3A7H)
Torque Reference/
Torque Limit
Selection from
Comm. Option
0: Disabled. Torque reference/limit from the host controller disabled.
1: Enabled. Torque reference/limit from the host controller enabled.
Default: 0
Min: 0
Max: 1
F6-07
(3A8H)
NetRef/ComRef
Function Selection
0: Multi-step reference disabled
1: Multi-step reference enabled
Default: 0
Min: 0
Max: 1