2.5 E: Motor Parameters
160
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
u
E3: V/f Pattern for Motor 2
These parameters set the V/f pattern used for motor 2. Refer to
Setting 16: Motor 2 Selection on page 176
for details on
switching motors.
n
E3-01: Motor 2 Control Mode Selection
Selects the control mode for motor 2.
Note: 1.
E3-01 dependent parameters are reset to the default settings when E3-01 is changed.
2.
Protection from motor overload (oL1) is determined by L1-01, just as it is for motor 1.
Setting 0: V/f Control
Setting 2: Open Loop Vector Control
Setting 3: Closed Loop Vector Control
n
E3-04 to E3-13
Parameters E3-04 through E3-13 set up the V/f pattern used for motor 2 as shown in
Figure 2.43
Figure 2.43 V/f Pattern for Motor 2
Note: 1.
The following conditions must be true when setting up the V/f pattern: E3-09 £ E3-07 < E3-06
≤
E3-11
≤
E3-04
2.
To make the V/f pattern a straight line at a frequency lower than E3-06, set E3-09 = E3-07. With this setting, E3-08 is disregarded.
3.
Parameters E3-04 through E3-13 are reset to their default values when the drive is initialized.
4.
E3-11, E3-12, and E3-13 rarely need to be changed, and should only be used to fine-tune the V/f pattern in the constant output range.
No.
Name
Setting Range
Default
E3-01
Motor 2 Control Mode Selection
0, 2, 3
2
No.
Name
Setting Range
Default
E3-04
Motor 2 Maximum Output Frequency
<1> Default setting is determined by the control mode selected for motor 2 (E3-01).
<2> The drive sets this value when Auto-Tuning is performed (Rotational Auto-Tuning and Stationary Auto-Tuning).
<3> Parameter ignored when E3-11 and E3-12 are set to 0.0.
<4> When Auto-Tuning for motor 2 is performed, E3-13 and E3-05 will be set to the same value.
<5> Default setting is determined by A1-02, Control Method Selection.
40.0 to 120.0 Hz
E3-05
Motor 2 Maximum Voltage
0 to 13000 V
E3-06
Motor 2 Base Frequency
0.0 to 120.0 Hz
E3-07
Motor 2 Mid Output Frequency
0.0 to 120.0 Hz
E3-08
Motor 2 Mid Output Frequency Voltage
0 to 13000 V
E3-09
Motor 2 Minimum Output Frequency
0.0 to 120.0 Hz
E3-10
Motor 2 Minimum Output Voltage
0 to 13000 V
E3-11
Motor 2 Mid Output Frequency 2
0.0 to120.0 Hz
E3-12
Motor 2 Mid Output Frequency Voltage 2
0 to 13000 V
0 V
E3-13
Motor 2 Base Voltage
0 to 13000 V
0 V
Output (V)
Frequency (Hz)
E3-05
E3-12
E3-13
E3-08
E3-10
E3-09
E3-07
E3-06 E3-11 E3-04
common_TMonly
MV1000ParameterGuide_E_conditional.book 160 ページ 2013年10月11日 金曜日 午後8時18分