1.3 Parameter Table
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
83
U6-07
(5FH)
q-Axis ACR
Output
Displays the output value for current control relative to motor secondary
current (q-axis).
10 V: Drive
rated voltage
0.1%
–
U6-08
(60H)
d-Axis ACR
Output
Displays the output value for current control relative to motor secondary
current (d-axis).
10 V: Drive
rated voltage
0.1%
–
U6-18
(7CDH)
Speed Detection
PG1 Counter
Monitors the number of pulses for speed detection (PG1).
10 V: 65536
1 pulse
U6-19
(7E5H)
Speed Detection
PG2 Counter
Monitors the number of pulses for speed detection (PG2).
10 V: 65536
1 pulse
U6-20
(7D4H)
Frequency
Reference Bias
(Up/Down 2)
Displays the bias value used to adjust the frequency reference.
10 V: Max
frequency
0.1%
–
U6-21
(7D5H)
Offset Frequency
Displays the frequency added to the main frequency reference.
–
0.1%
–
U6-80 to
U6-99
(7B0 to
7B9, 7F0
to 7F9H)
Option Monitor
1 to 20
Displays a monitor value of option cards.
No signal output
available
–
–
U9: Power Cell Monitors
U9-01
(3400H)
Power Cell
Status 1
Displays the status 1 of each of the Power Cells in hexadecimal.
Bit 0 to F: ASIC status
No signal output
available
–
–
U9-02
(3410H)
Power Cell
Status 2
Displays the status 2 of each of the Power Cells in hexadecimal.
Bit 0 to F: Fault information 1
No signal output
available
–
–
U9-03
(3420H)
Power Cell
Status 3
Displays the status 3 of each of the Power Cells in hexadecimal.
Bit 0 to F: Fault information 2
No signal output
available
–
–
U9-04
(3430H)
Power Cell
Status 4
Displays the status 4 of each of the Power Cells in hexadecimal.
Higher two digits (8 bits): Switching
Lower two digits (8 bits): Number of communication errors
No signal output
available
–
–
U9-05
(3440H)
Power Cell DC
Bus Voltage 1
Displays the DC bus voltage 1 (Vpc) of each Power Cell.
10 V: 2000 V
1 V
–
U9-06
(3450H)
Power Cell DC
Bus Voltage 2
Displays the DC bus voltage 2 (Vcn) of each Power Cell.
10 V: 2000 V
1 V
–
U9-07
(3460H)
Power Cell
Temperature
Displays the temperature of each Power Cell.
10 V: 200
°
C
0.01
°
C
–
U9-08
(3470H)
Power Cell
Output Current
Displays the output current of each Power Cell.
10 V: Drive
rated current
0.1 A
–
U9-09
(3480H)
Power Cell
Software No.
(CPU)
Displays the CPU ID of each Power Cell.
No signal output
available
–
–
U9-10
(3490H)
Power Cell
Software No.
(FPGA)
Displays the FPGA ID of each Power Cell.
No signal output
available
–
–
<60> V/f Control: 10 V: drive rated power (kW), OLV and CLV: 10 V: motor capacity (E2-11)
No.
(Addr.)
Name
Description
Analog Output
Level
Unit
Page
CLV
V/f
OLV
common
CLV
V/f
OLV
common
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_TMonly
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
All Modes
common_
MV1000ParameterGuide_E_conditional.book 83 ページ 2013年10月11日 金曜日 午後8時18分