2.6 F: Option Settings
YASKAWA ELECTRIC
TOEP C710687 03B FSDrive-MV1000 Parameter Guide
169
u
F6 and F7: Communication Option Card Settings
These parameters configure communication option cards and set the fault detection methods.
Some parameters apply to all communication option cards and some parameters apply to certain network options only.
The option cards are applicable to the parameter rows marked with an “O”.
n
F6-01: Communications Error Operation Selection
Determines drive operation when a communication error occurs.
Setting 0: Ramp to stop (uses the deceleration time set to C1-02)
Setting 1: Coast to stop
Setting 2: Fast Stop (uses the Fast Stop time set to C1-09)
Setting 3: Alarm only (continue operation)
n
F6-02: External Fault from Comm. Option Detection Selection
Determines the detection method of an external fault initiated by a communication option (EF0).
Setting 0: Always detected
Setting 1: Detection during run only
n
F6-03: External Fault from Comm. Option Operation Selection
Determines the operation when an external fault is initiated by a communication option (EF0).
Setting 0: Ramp to stop
Setting 1: Coast to stop
Setting 2: Fast Stop
Setting 3: Alarm only (continue operation)
Parameter
Communication Protocol
PROFIBUS-DP
DeviceNet
Modbus TCP/IP
F6-01 to F6-03
{
{
{
F6-04
–
–
–
F6-06 to F6-08
{
{
{
F6-30 to F6-32
{
–
–
F6-50 to F6-63
–
{
–
F7-01 to F7-15
–
–
{
F7-16
–
–
{
F7-17 to F7-42
–
–
–
No.
Parameter Name
Setting Range
Default
F6-01
Communications Error Operation Selection
0 to 3
1
No.
Parameter Name
Setting Range
Default
F6-02
External Fault from Comm. Option Detection Selection
0 or 1
0
No.
Parameter Name
Setting Range
Default
F6-03
External Fault from Comm. Option Operation Selection
0 to 3
1
MV1000ParameterGuide_E_conditional.book 169 ページ 2013年10月11日 金曜日 午後8時18分