Programming 78
H4 Analog Outputs
H4-01 Terminal FM Monitor Selection
Setting Range:
1 to 53
Factory Default: 2: Output Freq
The FM and AM analog output terminals can be programmed to output a 0-10 Vdc signal proportional to any one of functions
detailed in the table below.
When the H4-01 or H4-04 are configured the Drive will output 10Vdc to represent 100% of the function programmed into
them.
Fig. 59 Analog Output Signal Level as a Function of the Monitor Value
Function: Frequency Ref
Setting: 1
The analog output level will correspond to the chosen Speed Command input whether it is input via the digital operator, analog
input, or serial communication. 100% will be equivalent to the maximum output frequency of the Drive (E1-04).
Table 19
Setting
Description
Setting
Description
1
Frequency Ref
20
SFS Output*
2
Output Freq
24
PI Feedback
3
Output Current
31
Not Used
6
Output Voltage
36
PI Input
7
DC Bus Voltage
37
PI Output
8
Output kWatts
38
PI Setpoint
15
Term A1 Level
51
Auto Mode Fref
16
Term A2 Level
52
Hand Mode Fref
18
Mot SEC Current
53
PI Feedback 2
* SFS is the internal soft starter signal. This signal is generated from the reference and often it passes through the accel/ decel functions.
10 V
100%
0
Out
put
V
ol
tage
Monitor
Function Level