Programming 30
C6-02 Carrier Frequency Selection
Parameter C6-02 sets the switching frequency of the Drive’s output transistors. It can be changed in order to reduce audible
noise and also reduce leakage current. Cases that may require adjustment to the C6-02 are:
•
If the wiring length between the Drive and the motor is long, decrease the carrier frequency
•
If speed and torque are inconsistent at low speeds, decrease the carrier frequency
•
If leakage current from the Drive is large, decrease the carrier frequency
•
If the audible motor noise is too great, increase the carrier frequency (may require Drive current derating)
When parameter C6-02 is set to “0: Low Noise” the Drive uses a carrier frequency of 2 kHz and reduces the motor audible
noise by approximately 5 db. over the conventional 2 kHz setting (C6-02= 1). The Drive modulates the nominal PWM pattern
to achieve the lower noise. This setting is normally used with high starting torque loads that are frequently started and stopped
or, applications where leakage current needs to be minimized and motor audible noise is important.
Setting
Description
0
Low Noise
1
Fc=2.0 kHz
2
Fc=5.0 kHz
3
Fc=8.0 kHz
4
Fc=10.0 kHz
5
Fc=12.5 kHz
6
Fc=15.0 kHz
F
Program
*The factory default setting is model dependent
Wiring Length
164 ft or less
328 ft or less
Over 328 ft
C6-02 (carrier frequency) setting
1 to 6 (15 kHz max.)
1 to 4 (10 kHz max.)
1 to 2 (5 kHz max.)
Table 3 Carrier Frequency Parameter Factory Defaults (C6-01=2: Normal Duty 2)
208V-240V Drives 1
480V Drives 1
Model
CIMR-
E7U
C6-02
Carrier
Frequency
(kHz)
C6-03
Carrier
Frequency
Max.
(kHz)
C6-04
Carrier
Frequency
Min.
(kHz)
C6-05
Carrier
Frequency
Gain
Nominal
HP
Model
CIMR-
E7U
C6-02
Carrier
Frequency
(kHz)
C6-03
Carrier
Frequency
Max.
(kHz)
C6-04
Carrier
Frequency
Min.
(kHz)
C6-05
Carrier
Frequency
Gain
Nominal
HP
20P4
4 (10.0)
4 (10.0)
4 (10.0)
0
0.5/0.75
40P4
6 (15.0)
6 (15.0)
6 (15.0)
0
0.5/0.75
20P7
4 (10.0)
4 (10.0)
4 (10.0)
0
1
40P7
6 (15.0)
6 (15.0)
6 (15.0)
0
1
21P5
4 (10.0)
4 (10.0)
4 (10.0)
0
1.5/2
41P5
6 (15.0)
6 (15.0)
6 (15.0)
0
1.5/2
22P2
3 (8.0)
3 (8.0)
3 (8.0)
0
3
42P2
6 (15.0)
6 (15.0)
6 (15.0)
0
3
23P7
4 (10.0)
4 (10.0)
4 (10.0)
0
5
43P7
6 (15.0)
6 (15.0)
6 (15.0)
0
5
25P5
6 (15.0)
6 (15.0)
6 (15.0)
0
7.5
45P5
6 (15.0)
6 (15.0)
6 (15.0)
0
7.5
27P5
6 (15.0)
6 (15.0)
6 (15.0)
0
10
47P5/49P0
6 (15.0)
6 (15.0)
6 (15.0)
0
10/15
2011
3 (8.0)
3 (8.0)
3 (8.0)
0
15
4011
3 (8.0)
3 (8.0)
3 (8.0)
0
15/20
2015
4 (10.0)
4 (10.0)
4 (10.0)
0
20
4015
4 (10.0)
4 (10.0)
4 (10.0)
0
25
2018
4 (10.0)
4 (10.0)
4 (10.0)
0
25
4018/4024
4 (10.0)
4 (10.0)
4 (10.0)
0
30/40
2022
4 (10.0)
4 (10.0)
4 (10.0)
0
30
4030
3 (8.0)
3 (8.0)
3 (8.0)
0
40/50
2030
4 (10.0)
4 (10.0)
4 (10.0)
0
40
4037
3 (8.0)
3 (8.0)
3 (8.0)
0
60
2037
2 (5.0)
2 (5.0)
2 (5.0)
0
50
4045
3 (8.0)
3 (8.0)
3 (8.0)
0
75
2045
2 (5.0)
2 (5.0)
2 (5.0)
0
60
4055
2 (5.0)
2 (5.0)
2 (5.0)
0
100
2055
3 (8.0)
3 (8.0)
3 (8.0)
0
75
4075
2 (5.0)
2 (5.0)
2 (5.0)
0
125
2075
1 (2.0)
1 (2.0)
1 (2.0)
0
75/100
4090
3 (8.0)
3 (8.0)
3 (8.0)
0
150
2090
1 (2.0)
1 (2.0)
1 (2.0)
0
125
4110
2 (5.0)
2 (5.0)
2 (5.0)
0
200
2110
1 (2.0)
1 (2.0)
1 (2.0)
0
150
4160
2 (5.0)
2 (5.0)
2 (5.0)
0
250
4185
1 (2.0)
1 (2.0)
1 (2.0)
0
300/350
4220
1 (2.0)
1 (2.0)
1 (2.0)
0
450
4300
1 (2.0)
1 (2.0)
1 (2.0)
0
500+
Содержание E7U
Страница 1: ...E7 Drive Programming Manual Model E7U Document Number TM E7 02...
Страница 140: ...Programming 134 Notes...
Страница 170: ...Parameters A 30 Notes...
Страница 174: ...Factory Default Settings B 4 Notes...