Programming 107
L3-06 Stall Prevention Level During Running
Setting Range:
30 to 200% of Drive rated output current
Factory Default: 120% of Drive rated output current
The Stall Prevention During Running function will attempt to avoid a Drive OC fault occurrence while the Drive is operating
at a constant speed. If L3-05= “0: Disabled”, the Drive may fault if the load increases sufficiently to cause the output current to
reach the OC fault level (180% of Drive rated output current).
If L3-05= “1: General Purpose”, the Drive is outputting a constant speed, and the Drive’s output current level exceeds the level
set by parameter L3-06 for more than 100 ms the Drive will begin to decelerate at the rate specified by parameter C1-02. The
Drive will continue to decelerate until the output current level drops below the L3-06 level (less a 2% hysteresis). Once the
output current drops below the L3-06 – 2% level the Drive will begin to accelerate at the currently active acceleration rate
(either C1-01 or C1-03).
If L3-05= “2: Decel Time 2”, the Drive will function as described above except C1-04 will be used instead of C1-02 as the
deceleration rate used when the output current exceeds L3-06 for more than 100 ms.
The following figure demonstrates acceleration when L3-05
≠
0.
Fig. 78 Time Chart for Stall Prevention Level During Running
The L3-06 parameter is set as a percentage of the Drive rated output current. If the Drive still faults when L3-05
≠
0, then either
lower the L3-06 or adjust the C1-02 or C1-04 settings for a quicker deceleration.
a
L3-06
t
Output
Frequency
Output
Current
b
a
- Decel time
C1-02 or C1-04.
b
– Active accel time
t
b
a
a - Decel time
C1-02 or C1-04
b - Active Accel time
TIME