Programming 100
L1-02 Motor Overload Protection Time
Setting Range:
0.1 to 20.0 Minutes
Factory Default: 8.0 Minutes
The L1-02 parameter will set the allowed operation time before the OL1 fault will occur when the Drive is running at 60 Hz
and 133% of the motor’s full load amp rating (E2-01). Adjusting the value of L1-02 can shift the set of OL1 curves up the
Y-axis of the diagram below but will not change the shape of the curves.
Fig. 72 Motor Overload Protection Time based on Output frequency and Load
125%
4
2
Time
(M
inut
es
)
Output Current
(Percent of motor FLA)
E2-01 200%
6
8
10
60Hz
10Hz
175%
150%