![YASKAWA E7U Скачать руководство пользователя страница 53](http://html1.mh-extra.com/html/yaskawa/e7u/e7u_programming-manual_3477696053.webp)
Programming 47
Function: 3-Wire Control
Setting: 0
When one of the digital inputs is programmed for 3-Wire control, that input becomes a Forward/Reverse directional input.
Whenever the input is open, the Drive will be set for forward rotation of the motor shaft. If the input it closed, then the motor
shaft will rotate in the reverse direction whenever a there is a Run input. The S1 and S2 digital inputs will function as a Run
and Stop input respectively.
Fig. 30 Terminal Configuration for 3-Wire Control
Fig. 31 3-Wire Control Timing Diagram
Function: Local/Remote Selection
Setting: 1
This function has been disabled. Please refer settings “6D” and “6E”.
IMPORTANT
As long as the S1(Run Command) input is applied in for at least 50 ms the Run command will latch
internally in the Drive.
S5
SN
Stop
switch
(NC contact)
Operation
switch
(NO contact)
Run command
(run on momentary close)
Stop command
(stop on momentary open)
Forward / reverse command
(multi-function input)
Sequence input common
50 ms min.
Run command
Forward/reverse
command
Motor speed
Can be either ON or OFF
OFF
(stopped)
OFF (forward)
ON (reverse)
Stop
Forward
Reverse
Stop
Forward
Stop command
TIME