![YASKAWA E7U Скачать руководство пользователя страница 173](http://html1.mh-extra.com/html/yaskawa/e7u/e7u_programming-manual_3477696173.webp)
Factory Default Settings B - 3
Table B.2 480VAC Drives
Drive Model
CIMR-E7U
Nominal
Hp
Factory
Default
for
b8-04
Factory
Default
for
C6-02
Factory
Default
for
E2-01
Factory
Default
for
E2-03
Factory
Default
for
E2-05
Factory
Default
for
L2-02
Factory
Default
for
L2-03
Factory
Default
for
L2-04
Factory
Default
for
L8-02
Factory
Default
for
L8-06
40P4
0.5/0.75
576.40
15kHz
1.0
0.6
38.198
0.1
0.1
0.3
95°C
5
40P7
1
447.40
15kHz
1.6
0.8
22.459
0.1
0.2
0.3
95°C
7.5
41P5
1.5/2
338.80
15kHz
3.1
1.4
10.100
0.2
0.3
0.3
95°C
10
42P2
3
313.60
15kHz
4.2
1.5
6.495
0.3
0.4
0.3
90 °C
10
43P7
5
245.80
15kHz
7.0
2.3
3.333
0.5
0.5
0.3
95°C
12
45P5
7.5
189.50
15kHz
13.3
2.6
1.595
1.0
0.6
0.3
95°C
10
47P5
10
145.38
15kHz
19.9
4.0
1.152
1.0
0.7
0.3
90°C
20
49P0
15
145.46
15kHz
21.0
4.4
0.922
1.0
0.8
0.3
95°C
23
4011
15/20
140.88
8kHz
26.5
5.6
0.922
2.0
0.8
0.3
95°C
23
4015
25
126.26
10kHz
32.9
7.6
0.550
2.0
0.9
0.3
95°C
17
4018
30
115.74
10kHz
52.3
7.8
0.403
2.0
1.0
0.6
98°C
17
4024
40
89.08
10kHz
52.0
8.6
0.269
2.0
1.1
0.6
85°C
20
4030
40/50
92.54
8kHz
65.6
10.9
0.269
2.0
1.1
0.6
85°C
20
4037
60
76.32
8kHz
79.7
19.1
0.155
2.0
1.1
0.6
85°C
20
4045
75
71.56
8kHz
95.0
22.0
0.122
2.0
1.2
0.6
90°C
20
4055
100
67.20
5kHz
130.0
24.0
0.088
2.0
1.2
1.0
90°C
20
4075
125
46.20
5kHz
130.0
36.0
0.092
2.0
1.3
1.0
98°C
16
4090
150
38.91
8kHz
156.0
40.0
0.056
2.0
1.5
1.0
108°C
16
4110
200
36.23
5kHz
190.0
49.0
0.046
2.0
1.7
1.0
100°C
16
4160
250
30.13
5kHz
270.0
70.0
0.029
2.0
1.8
1.0
108°C
14
4185
300/350
30.57
2kHz
310.0
81.0
0.025
2.0
0.7
1.0
95°C
15
4220
400/450
27.13
2kHz
370.0
96.0
0.020
2.0
0.8
1.0
100°C
15
4300
500+
21.76
2kHz
500.0
130.0
0.014
2.1
0.9
1.0
95°C
15
Note: b8-04 = Energy Savings Coefficient
C6-02 = Carrier Frequency
E2-01 = Motor Rated Current
E2-03 = Motor No-Load Current
E2-05 = Motor Line-to-Line Resistance
L2-02 = Momentary Power Loss Ride-Thru Time
L2-03 = Momentary Power Loss Minimum Base Block Time
L2-04 = Momentary Power Loss Voltage Recovery Ramp Time
L8-02 = Overheat Pre-Alarm Level
L8-06 = Input Phase Loss Detection Level
Содержание E7U
Страница 1: ...E7 Drive Programming Manual Model E7U Document Number TM E7 02...
Страница 140: ...Programming 134 Notes...
Страница 170: ...Parameters A 30 Notes...
Страница 174: ...Factory Default Settings B 4 Notes...