Programming 125
o2-04 Drive / kVA Selection
Setting Range:
0 to FF
Factory Default: Model Dependent
Parameter o2-04 matches the control board to the Drive hardware. Proper setting of o2-04 is important so that the control
board can provide proper protection for the Drive hardware. This parameter is configured at the factory and does not normally
require adjustment in the field. It is available primarily to accommodate control board replacement in the event of damage.
The factory defaults of the following parameters may be changed when the setting of o2-04 is changed:
•
b8-04 (Energy Saving Coefficient Value)
•
C6-02 (Carrier Frequency Selection)
•
E2-01 (Motor Rated Current)
•
E2-03 (Motor No-Load Current)
•
E2-05 (Motor Line-to-Line Resistance)
•
L2-02 (MPL Ride-Thru Time)
•
L2-03 (MPL Minimum Base Block Time)
•
L2-04 (MPL Voltage Recovery Ramp Time)
•
L8-02 (Overheat Pre-Alarm Level)
•
L8-06 (Input Phase Loss Detection Level)
Table 31 KVA Settings by Drive Model Number
208-230/240Vac
480Vac
Model Number
Proper
o2-04 Setting
Model Number
Proper
o2-04 Setting
20P4
0
40P4
20
20P7
1
40P7
21
21P5
2
41P5
22
22P2
3
42P2
23
23P7
4
43P7
24
27P5
6
45P5
26
2011
7
47P5
27
2015
8
49P0
3C
2018
9
4011
28
2022
A
4015
29
2030
B
4018
2A
2037
C
4022
2B
2045
D
4024
3D
2055
E
4030
2C
2075
F
4037
2D
2090
10
4045
2E
2110
11
4055
2F
4075
30
4090
31
4110
32
4160
34
4185
35
4220
36
4300
37