6 Utility Functions (Fn
)
6-16
6.6
Initializing Parameter Settings (Fn005)
This function is used when returning to the factory settings after changing parameter settings.
Note: Any value adjusted with Fn00C, Fn00D, Fn00E, and Fn00F cannot be initialized by Fn005.
(1) Preparation
The following conditions must be met to initialize the parameter values.
• The write prohibited setting parameter (Fn010) must be set to Write permitted (P.0000).
• The servomotor power must be OFF.
(2) Operating Procedure
Use the following procedure.
1.
In the S main window, click
Parameters
-
Edit Parameters
.
The
Parameter Editing
dialog box will appear.
• Be sure to initialize the parameter settings while the servomotor power is OFF
.
• After initialization, restart the SERVOPACK to validate the settings.