9 Output Assemblies (Drive Consumes)
26
YASKAWA ELECTRIC
SIEP C730600 43A YASKAWA AC Drive-Option Card DeviceNet Technical Manual
Note:
This is a paired assembly (105/155).
Table 11 Function Code Decode Table
Note:
Refer to the MEMOBUS/Modbus Data Table in Appendix C of the technical Manual for the drive the DeviceNet Option is
connected to for a list of monitor data using the MEMOBUS/Modbus message area.
Multi-Function Input 6
Terminal S6 Function Input
0: Terminal S6 Function (H1-06) OFF
1: Terminal S6 Function (H1-06) ON
Multi-Function Input 7
Terminal S7 Function Input
0: Terminal S7 Function (H1-07) OFF
1: Terminal S7 Function (H1-07) ON
Multi-Function Input 8
Terminal S8 Function Input
0: Terminal S8 Function (H1-08) OFF
1: Terminal S8 Function (H1-08) ON
External Fault
External Fault EF0
0: No External Fault (EF0)
1: External Fault (EF0)
Fault Reset
Fault Reset
0: No Fault Reset
1: Fault Reset
Function Code
MEMOBUS/Modbus Function Code
Refer to Function Code Decode Table on page 26
.
Multi-Function Digital Output
Terminal M1/M2
0: M1/M2 OFF
1: M1/M2 ON
This function is enabled only when H2-01 is set to F.
Multi-Function Photo Coupler 1
Terminal P1
0: P1 OFF
1: P1 ON
This function is enabled only when H2-02 is set to F.
Multi-Function Photo Coupler 2
Terminal P2
0: P2 OFF
1: P2 ON
This function is enabled only when H2-03 is set to F.
Speed Reference
Speed Command
Sets drive speed reference
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Register Number
MEMOBUS/Modbus Register Number
Register Data
MEMOBUS/Modbus Register Data
<1> Register numbers 0x0001, 0x0002, and 0x0009 are disabled.
Function Code
High Byte - Low Byte
MEMOBUS/Modbus Function
0 0
No Operation
1 0
Read Register
0 1
Write Register
1 1
No Operation
Name
Description