10 Input Assemblies (Drive Produces)
YASKAWA ELECTRIC
SIEP C730600 43A YASKAWA AC Drive-Option Card DeviceNet Technical Manual
37
10
Input Assemblies (Drive Produces)
Note:
The convention in this manual is from the PLC perspective. As such, an assembly is called an “Output Assembly” when
outputted from the PLC and received by this node. An “Input Assembly” is outputted from this node and read by the PLC. This
section details “Intput Assemblies” that are “Produced” by this drive.
Basic Speed Control Input - 70 (0x46)
Note:
The control mode (A1-02) determines whether the value for the speed monitor is either the output frequency or the actual motor
speed.
Extended Speed Control Input - 71 (0x47)
Input
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
70
0
–
–
–
–
–
Running 1
(FWD)
–
Faulted
1
–
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
Parameter
Data
Faulted
Faulted
0: No Faults Occurred
1: Fault Occurred
Running1
Forward Running
0: Stop or Reverse Running
1: Forward Running
Speed Actual
Actual Drive Speed
Monitors drive output frequency
Speed actual data: Output frequency
×
2
SS
(SS: Speed scale)
Range: 0 to 0xFFFF
For example, when output frequency of 4096 with a speed scale of 2
Speed actual data = 4096
×
2
2
= 16384 = 0x4000
Unit depends on o1-03.
Control Mode (A1-02)
Speed Actual
0
V/f
Output Frequency
0
(H6-01 = 3)
V/f with Simple PG
Motor Speed
1
V/f with PG
Motor Speed
2
OLV
Motor Speed
3
CLV
Motor Speed
5
OLV for PM Motor
Output Frequency
6
Advanced OLV for PM motor
Motor Speed
7
CLV for PM Motor
Motor Speed
Input
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
71
0
At Speed
Ref from Net Ctrl from Net
Ready
Running 2
(REV)
Running 1
(FWD)
Warning
Faulted
1
State
2
Speed Actual (Low Byte)
3
Speed Actual (High Byte)
Name
Description
Faulted
Faulted
0: No Faults Occurred
1: Fault Occurred