10 Input Assemblies (Drive Produces)
YASKAWA ELECTRIC
SIEP C730600 43A YASKAWA AC Drive-Option Card DeviceNet Technical Manual
43
Speed Status Dynamic Assy (Vendor Specific YE Assy) - 134 (0x86)
ZSV
Zero Servo Completed
0: –
1: Completed
Actual Current
Actual Output Current
Monitors drive output current
Unit is 0.01 A for drives set up to 11 kW in Heavy Duty or Normal Duty and 0.1 A for drives set up for 15
kW and above.
Unit is not affected by Current Scale CS.
Output Frequency
Actual Drive Speed
Monitors drive output frequency
Unit depends on o1-03.
Unit is not affected by Speed Scale SS.
Input
Instance
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
134
0
FAULT
ALARM
READY
Speed
Agree
Reset
REV
Running
ZSP
Running
1
Service Code
2
Class
3
Attribute
4
Data (Low Byte)
5
Data (High Byte)
6
Output Frequency (Low Byte)
7
Output Frequency (High Byte)
Parameter
Data
Running
Running
0: Stop
1: Forward or Reverse Running
ZSP
Zero Speed
0: Running
1: Stop or DC Injection Braking
REV Running
Reverse Running
0: Not Reverse Running
1: Reverse Running
Reset
Reset
0: No Reset
1: Reset
Speed Agree
Speed Agree
0: No Speed Agree
1: Actual speed at speed reference
READY
Drive Ready
0: Not Ready
1: Ready
ALARM
Drive Alarm
0: No Drive Alarm
1: Alarm
FAULT
Drive Fault
0: No Drive Fault
1: Fault
Service Code
Service Code
Refer to Service Code Decode Table on page 34
Class
Class
Valid Classes are Control Supervisor Object (41) and AC/DC Object (42).
Instance will always be 1.
Attribute
Attribute
Data
Data
If Service Code is 0x94, Data is Error Code.
Parameter
Data