7 Configuring DeviceNet Messaging
YASKAWA ELECTRIC
SIEP C730600 43A YASKAWA AC Drive-Option Card DeviceNet Technical Manual
17
7
Configuring DeviceNet Messaging
This section provides information on the various methods used to control the drive on DeviceNet.
Drive Configuration on DeviceNet
Polled Configuration
The Drive DeviceNet Polled connection must be configured before receiving commands from a Master device. The two
parameters that must be configured are:
• F6-52: Polled Consuming Assembly (PCA)
Note:
Output assembly consumed by the drive.
• F6-53: Polled Producing Assembly (PPA)
Note:
Input assembly produced by the drive.
The default connection paths for the DeviceNet Option are set for Extended Speed Control.
The PCA and PPA parameters can be accessed by two methods.
• A software configuration tool (not supplied), and Yaskawa Electronic Data Sheet (EDS)
Note:
The PCA and PPA parameters can be accessed from the “DN: Polled Config” parameter group.
• A software configuration tool (not supplied), via a DeviceNet message path, such as (Extended Speed Control)
Note:
Use DeviceNet Connection Object to change the PCA or PPA if required by the application (Class 5, Instance 1, Attributes 14
and 16)
One each PCA and PPA assembly from the following table must be selected to configure the drive for polled operation.
Table 9 Supported Polled Assemblies (PCA and PPA)
Assembly
Number (decimal)
Description
Type Bytes Page
20
Basic Speed Control Output - 20 (0x14)
PCA
4
21
Extended Speed Control Output - 21 (0x15)
(Default Setting)
PCA
4
22
Speed and Torque Control Output - 22 (0x16)
PCA
6
23
Extended Speed and Torque Control Output - 23 (0x17)
PCA
6
70
Basic Speed Control Input - 70 (0x46)
PPA
4
71
Extended Speed Control Input - 71 (0x47)
(Default Setting)
PPA
4
72
Speed and Torque Control Input - 72 (0x48)
PPA
6
73
Extended Speed and Torque Control Input - 73 (0x49)
PPA
6
100
MEMOBUS/Modbus Message Command (Vendor Specific YE Assy) - 100 (0x64)
PCA
5
101
Standard Control (Vendor Specific YE Assy) - 101 (0x65)
PCA
8
102
Accel/Decel Time (Vendor Specific YE Assy) - 102 (0x66)
PCA
8
105
Enhanced Speed Control, Dynamic (Vendor Specific YE Assy) - 105 (0x69)
PCA
8
106
Enhanced Control (Vendor Specific YE Assy) - 106 (0x6A)
PCA
8
107
Standard DI/DO Control (Vendor Specific YE Assy) - 107 (0x6B)
PCA
8
108
Enhanced Torque Control, Dynamic (Vendor Specific YE Assy) - 108 (0x6C)
PCA
8
120
Speed Command 1 (Vendor Specific YE Assy) - 120 (0x78)
PCA
4
121
Torque Command 1 (Vendor Specific YE Assy) - 121 (0x79)
PCA
4
122
Speed Command 2 (Vendor Specific YE Assy) - 122 (0x7A)
PCA
6
123
Torque Command 2 (Vendor Specific YE Assy) - 123 (0x7B)
PCA
6
124
Speed Dynamic Assy (Vendor Specific YE Assy) - 124 (0x7C)
PCA
8
125
Torque Dynamic Assy (Vendor Specific YE Assy) - 125 (0x7D)
PCA
8
126
Speed/Torque Assy (Vendor Specific YE Assy) - 126 (0x7E)
PCA
8
130
Speed Status (Vendor Specific YE Assy) - 130 (0x82)
PPA
4
131
Current Status (Vendor Specific YE Assy) - 131 (0x83)
PPA
4
132
Current & Speed Status (Vendor Specific YE Assy) - 132 (0x84)
PPA
6
134
Speed Status Dynamic Assy (Vendor Specific YE Assy) - 134 (0x86)
PPA
8
135
Current Status Dynamic Assy (Vendor Specific YE Assy) - 135 (0x87)
PPA
8
136
Torque and Speed Status (Vendor Specific YE Assy) - 136 (0x88)
PPA
8
150
MEMOBUS/Modbus Message Reply (Vendor Specific YE Assy) - 150 (0x96)
PPA
5
151
Standard Status 1 (Vendor Specific YE Assy) - 151 (0x97)
PPA
8