4 DeviceNet Option Components
YASKAWA ELECTRIC
SIEP C730600 43A YASKAWA AC Drive-Option Card DeviceNet Technical Manual
9
Power-Up Diagnostics
An LED test is performed each time the drive is powered up. The initial boot sequence may take several seconds. After
the LEDs have completed the DeviceNet diagnostic LED sequence, the DeviceNet Option is successfully initialized. The
LEDs then assume operational conditions as shown in
.
Table 4 Power-Up Diagnostic LED Sequence
Set the DeviceNet Option MAC ID
Parameter F6-50, MAC ID Setting
Range:
0~64
The MAC ID is set by drive parameter F6-50. A MAC ID setting in the range of 0~63 is considered a valid MAC ID. A
value other than 0~63 indicates the MAC ID is settable over the network.
The DeviceNet Option SI-N3 reads the MAC ID value from parameter F6-50 upon power-up and upon a network reset.
Set the DeviceNet Option Baud Rate
The DeviceNet Option will support standard baud rates of 125 k bit/s, 250 k bit/s, and 500 k bit/s.
Table 5 Parameter F6-51 Baud Rate Setting
Auto Baud Rate Sensing (F6-51 = 4)
Setting parameter F6-51 = 4, "Auto Detect" causes the DeviceNet Option to determine the data rate of the DeviceNet
Network and configure itself appropriately.
Note:
The auto baud capability will only be valid when there is more than one node physically on the DeviceNet network segment. The
drive digital operator will display “bUS” and the DeviceNet option LEDs will be (NS-OFF and MS=Solid Green) as long as auto
baud rate sensing fails to detect the baud rate.
NS
–
OFF
Offline or Power supply
OFF
–
Green ON
Online communications
established
Device is on-line and has connections in the established state.
Green
Flashing
Online communications not
established
Device is on-line but has no connections in the established state.
Dup Mac-ID test has been passed, is on-line but has no open
connections to other nodes.
Red ON
Communications
error
An error occurred that disables DeviceNet communications.
MAC ID duplication
Bus Off detected
Red Flashing
Communications time-out
A communications time-out occurred with the master.
Green/Red
Flashing
Communication faulted
Specific communication faulted device.
The device has detected a network access error and is in the
communications faulted state.
The device has then received and accepted an Identify communication
fault request-long protocol message.
Sequence
Module Status (MS)
Network Status (NS)
Time (ms)
1
GREEN
OFF
250
2
RED
OFF
250
3
GREEN
GREEN
250
4
GREEN
RED
250
5
GREEN
OFF
-
Description
Value
125 k bit/s
0
250 k bit/s
1
500 k bit/s
2
Programmable From Network
3
Auto Detect
4
Name
Indication
Operating Status
Remarks
Color
Status