User Constants
8.2.11 Factory Settings that Change with the Inverter Capacity (o2-04)
- 36
J
400 V Class Inverters
Con-
stant
No.
Name
Unit
Factory Setting
Inverter Capacity
kW
0.4
0.75
1.5
2.2
3.7
4.0
5.5
7.5
11
o2-04
kVA selection
1
20
21
22
23
24
25
26
27
28
C6-01
Carrier frequency upper limit *
kHz
15.0
15.0
15.0
15.0
15.0
15.0
15.0
12.5
12.5
Carrier frequency upper limit
range
kHz
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
E2-01
(E5-01)
Motor rated current
A
1.00
1.60
3.10
4.20
7.00
7.00
9.80
13.30
19.9
E2-02
(E5-02)
Motor rated slip
Hz
2.90
2.60
2.50
3.00
2.70
2.70
1.50
1.30
1.70
E2-03
(E5-03)
Motor no-load current
A
0.60
0.80
1.40
1.50
2.30
2.30
2.60
4.00
5.6
E2-05
(E5-05)
Motor line-to-line resistance
38.198
22.459
10.100
6.495
3.333
3.333
1.595
1.152
0.922
E2-06
(E5-06)
Motor leak inductance
%
18.2
14.3
18.3
18.7
19.3
19.3
18.2
15.5
19.6
L2-02
Momentary power loss ridethru
time
sec
1.0
1.0
1.0
1.0
2.0
2.0
2.0
2.0
2.0
L2-03
Min. baseblock time
sec
0.5
0.5
0.5
0.5
0.5
0.7
0.7
0.7
0.7
L2-04
Voltage recovery time
sec
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
Con-
stant
No.
Name
Unit
Factory Setting
Inverter Capacity
kW
15
18.5
22
30
37
45
55
75
o2-04
kVA selection
1
29
2A
2B
2C
2D
2E
2F
30
C6-01
Carrier frequency upper limit
kHz
12.5
12.5
10.0
10.0
10.0
7.0
6.0
6.0
Carrier frequency upper limit
range
kHz
15.0
15.0
15.0
15.0
10.0
10.0
10.0
10.0
E2-01
(E5-01)
Motor rated current
A
26.5
32.9
38.6
52.3
65.6
79.7
95.0
130.0
E2-02
(E5-02)
Motor rated slip
Hz
1.60
1.67
1.70
1.80
1.33
1.60
1.46
1.39
E2-03
(E5-03)
Motor no-load current
A
7.6
7.8
9.2
10.9
19.1
22.0
24.0
36.0
E2-05
(E5-05)
Motor line-to-line resistance
0.550
0.403
0.316
0.269
0.155
0.122
0.088
0.092
E2-06
(E5-06)
Motor leak inductance
%
17.2
20.1
23.5
20.7
18.8
19.9
20.0
20.0
L2-02
Momentary power loss ridethru
time
sec
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2.0
L2-03
Min. baseblock time
sec
0.7
1.0
1.0
1.0
1.0
1.0
1.0
1.0
L2-04
Voltage recovery time
sec
0.3
0.6
0.6
0.6
0.6
0.6
0.6
0.6
*
When frequency upper limit is set higher than the factory setting with the inverter of 7.5kW or more, inverter rated current should
be reduced. Contact your YASKAWArepresentative for details.
8