Basic Operation
6.1.3 Frequency Reference from Digital Operator: b1-01, o1-03, d1-01 to d1-09
- 8
J
Preset Frequency Reference Values: d1-01 through d1-09
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
Open Loop
Vector
Flux Vector
d1-01
Frequency reference 1
0 to 400.00
o1-03
0.00 Hz
Q
Q
d1-02
Frequency reference 2
0 to 400.00
o1-03
0.00 Hz
Q
Q
d1-03
Frequency reference 3
0 to 400.00
o1-03
0.00 Hz
Q
Q
d1-04
Frequency reference 4
0 to 400.00
o1-03
0.00 Hz
Q
Q
d1-05
Frequency reference 5
0 to 400.00
o1-03
0.00 Hz
B
B
d1-06
Frequency reference 6
0 to 400.00
o1-03
0.00 Hz
B
B
d1-07
Frequency reference 7
0 to 400.00
o1-03
0.00 Hz
B
B
d1-08
Frequency reference 8
0 to 400.00
o1-03
0.00 Hz
B
B
d1-09
Jog frequency reference
0 to 400.00
o1-03
6.00 Hz
Q
Q
D
The units for these values are set in o1-03.
D
The frequency reference default value and set value will change when o1-03 is changed.
For example, if preset reference 1 is set to 6.00 Hz and o1-03 is changed to 1 (0.01% units), the setting
for preset reference 1 will become 10.00%.
D
When using preset references 2 through 8, be sure to set multi-step speed references 1, 2, and 3 in the
multi-function inputs (H1-01 through H1-06) as required.
D
When using the jog function, set the jog frequency reference in constant d1-09. When jogging from
an external terminal, set the multi-function inputs (H1-01 through H1-06) to “Jog Frequency Refer-
ence,” “Forward Jog,” or “Reverse Jog” as required.
D
The multi-function input setting is unnecessary when jogging from the Operator.
6