Advanced Operation
7.3.6 Protective Functions: L
- 54
User
Constant
Number
Valid Access Levels
Factory
Setting
Unit
Setting
Range
Change
during
Opera-
tion
Name
User
Constant
Number
Flux Vector
Open Loop
Vector
Factory
Setting
Unit
Setting
Range
Change
during
Opera-
tion
Name
L4-03
Speed agree detection
level (+/--)
--400.0 to
+400.0
Hz
0.0
A
A
L4-04
Speed agree detection
width (+/--)
0.0 to 20.0
Hz
2.0
A
A
D
Set these constants when outputting one of the frequency agree or frequency detection signals from
a multi-function output. Table 7.10 shows the relationship between these constants and the output sig-
nals.
D
Motor speed is detected at Flux Vector Control.
Table
7.10
Constants and Output Signals
Constant
Related output settings
Constant function
Speed Agree Level
(Absolute value)
Fref/Set Agree 1
Frequency Detection 1 >
Frequency Detection 2 <
Set the frequency (or motor speed) that
you want to detect in Hz.
The set speed is an absolute value, so the
speed is detected in forward or reverse.
Speed Agree Width
(Absolute value)
Fref/Fout Agree 1
Fref/Set Agree 1
Frequency Detection 1 >
Frequency Detection 2 <
Set the frequency (or motor speed) detec-
tion range in Hz.
Speed Agree Level
+/--
(Signed value)
Fref/Set Agree 2
Frequency Detection 3 >
Frequency Detection 4 <
Set the frequency (or motor speed) that
you want to detect in Hz.
Set positive values for forward, negative
values for reverse.
Speed Agree Width
+/--
(Signed value)
Fref/Fout Agree 2
Fref/Set Agree 2
Frequency Detection 3 >
Frequency Detection 4 <
Set the frequency(or motor speed) detec-
tion range in Hz.
D
Set the corresponding setting in the multi-function output (H2-01, H2-02, or H2-03) to output the de-
sired Fref/Fout Agree signal, Fref/Set Agree signal, or Frequency Detection signal.
Function
Setting
Fref/Fout Agree 1
2
Fref/Set Agree 1
3
Frequency Detection 1
4
Frequency Detection 2
5
Fref/Fout Agree 2
13
Fref/Set Agree 2
14
Frequency Detection 3
15
Frequency Detection 4
16
Frequency Detection Operation: L4-05
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
Open Loop
Vector
Flux Vector
L4-05
Operation when fre-
quency reference is
missing
0 1
--
0
A
A
D
The frequency reference is considered lost when the frequency reference voltage drops by 90% for
more than 400 ms.
7