33
11. SPECIFICATIONS
Product Name
Neocool
®
circulator
Model
CF302L-A
System/circulating water
Closed circulation/tap water, antifreeze solution (below 10 °C)
Operating ambient temperature range
5 to 35 °C
P
e
rfo
rm
a
n
c
e
Temperature setting range *1
-20 to 30 °C
Temperature control accuracy
(JTM K05) *2
±1.0 °C (
≧
0 °C)
±1.5 °C (
<
0 °C)
Temperature fluctuation (JIS) *2
3.0 °C(
≧
0 °C)
4.0 °C(
<
0° C)
Cooling capacity
(liquid temp) *2
Approx. 420 W (at 10 °C)
Approx. 280 W (at -10 °C)
Max. flow rate *3
Approx. 10 L/min
Max. head *3
Approx. 5.7 m
C
o
n
fig
u
ra
tio
n
Temperature control system
Refrigerator ON-OFF
Temperature sensor
Pt100Ω
Controller
White LED digital display, key entry, minimum digit of 1 °C
Refrigeration system/Rated
performance/Refrigerant
Air-cooling/450 W/R404A
Cooling coil
Copper/Nickel plating
External circulation connection
port
Rear top panel, single line
One-touch connector (swivel type, L-type)
Flow rate valve (optional)
Circulation pump
15W
Safety functions
Overcurrent ELCB, temperature sensor failure, temperature
upper/lower limit alert, temperature upper/lower limit error,
refrigerator high-pressure cut-off switch, fan motor
protection, circulation pump protection, delay timer for
refrigerator protection
Other functions
Drain hose, condensate drain hose, Intake dust filter,
cooling operation key, circulating pump key, calibration
offset, Auto-resume function
S
ta
n
d
a
rd
Reservoir material
Capacity (liquid volume)
Stainless steel Approx. 3.9 L (3.5 L)
External dimensions
(including protrusions)
W205 × D396 × H535 mm
(W225 × D434 × H564 mm)
Power supply
Single phase 115 V AC
Current (ELCB capacity)
7.5 A (10A)
Power cable
2 m with a plug
Weight
Approx. 31 kg
Accessories
Instruction manual (1), Warranty card (1)
Condensate drain hose(1 m)(1), Hose clamp (2)
Hose nozzle (for flexible hose connection)(2)
*1 Unit
does not feature heating function. Depending on the ambient temperature or connection conditions,
temperature may not reach -20 °C.
*2
Performance based on 115 V AC supplied power and 20 °C ambient temperature.
Temperature control accuracy and Temperature fluctuation are standards calculated according to JTM K05
and JIS respectively.
*3
Pump performance based on tap water at 20 °C
Содержание Neocool CF302L-A
Страница 2: ......
Страница 5: ...1 1 SAFETY PRECAUTIONS Explanation of Symbols ...