16
4. INSTALLATION PROCEDURES
Installation Procedure
1. Hose connection
Connect hoses to the discharge port and return port of the cooling water circulation system.
CF series units are an external closed loop circulation system.
Connection can be made with 10 mm O.D. rigid hose, or with 9 mm I.D flexible hose. With optional
nozzle attached, other hoses can be connected. Select an appropriate hose according to the
purpose of equipment use.
Attach a 20-mesh filter to the return port if there is a risk of dust or foreign objects mixed into the
circulating water returning from the external device. See Strainer set in "List of Options" (P.37)
・
When using rigid hose with 10 mm O.D.
Put the supplied insert sleeve into rigid hose, and push the hose straight to the end while holding
the connection port with hand. Failure to use the insert sleeve may lead to water leakage.
To remove the hose, pull out the hose with the ring of the connection port pushed in.
・
When using a flexible hose with 9 mm I.D.
1. Connect the flexible hose securely to the hose nozzle (included).
2. Push the hose nozzle straight to the end while holding the connection port with hand.
3. Secure the flexible hose with a hose clamp.
Hose nozzle
(Included)
Connection port
(IN/OUT common)
Hose removal
Push-in
Ring
Flexible hose (optional)
(9 mm I.D.)
Connection port
(IN/OUT common)
Rigid hose (optional)
(10 mm O.D.)
Insert sleeve (included with rigid hose)
Hose clamp
(included with flexible hose)