18
4. INSTALLATION PROCEDURES
Installation Procedure
4. Filling water reservoir
Select circulating water according to "Preparation of circulating water" (P.15)
1. Open the lid and let circulating water flow into the reservoir
until the cooling coil is immersed.
2. In this state, turn ELCB ON (|) and press the Power switch to
operate and begin liquid circulation.
See "5. OPERATION PROCEDURES” (P.19)
3. The water level in the reservoir will decrease by the time
circulating path is filled up. Add circulating water until the
cooling coil is once again immersed.
Complete this work before operating the refrigerator.
4. Turn off ELCB when circulating water is sufficiently supplied.
When pouring circulating water, put it in gently without giving
a momentum. Note that when the circulation pump stops, the
water level in the reservoir will vary.
5. Replace reservoir cover.
Do not open the cover unless otherwise necessary to prevent
dust, foreign object, etc. from entering the reservoir.
Use caution not to let circulating water spill over unit.
Electric leakage or electric shock may result if the circulating
water comes into contact with the electrical components.
When circulating water spills on the control panel, wipe it dry
with a clean dry cloth.
5. Installation of condensate drain hose
1. Connect the condensate drain hose to the condensate
drain port on the back of unit.
2. Insert two supplied hose clamps into the holes on the right
side of unit. See "External view" (P.10) for locations.
3. Draw the condensate drain hose through hose clamp and
secure it.
4. Prepare a drip tray.
(Drip tray is not included and should be prepared separately)
5. Draw the condensate drain hose into the drip tray.
Drain and clean the drip tray on a regular basis.
Cooling coil
Condensate drain hose
Drip tray
Condensate
drain port
Hose clamp
* CF series units do not
feature overflow system. Be
careful not to overfill the
reservoir.