Yamatake Corporation
ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter
9
ST3000 Smart Pressure Transmitters Series 900
Complying with ATEX Directive
1. Intrinsic Safety
1. Certification
~Note
The apparatus is ensured to comply with the following European stan-
dards.
EN 50014 (Electrical apparatus for explosive gas atmospheres)
EN 50020 (Intrinsic safety “i”)
EN 50284 (Electrical apparatus for equipment group II, Category 1 G)
Certificate No.: KEMA 03ATEX1225 X
Specific type of protection: II 1 G EEx ia IIC T4
where each letter or symbol represents the meaning as follows.
II: Equipment group II (Equipment for use in places other than mines).
1:
Category 1 (Highest category equipment allowed to be installed in Zone
0).
G:
Gas ignition protection.
EEx: Apparatus being applied by one of the types of protection specified by
EN standards.
Ia:
Intrinsically safe apparatus with a level of protection “ia”.
IIC: Group IIC (The apparatus of IIC can be used in air-gas mixture of hydro-
gen or acetylene).
T4: Temperature class T4 (Surfaces of the apparatus of T4 do not exceed
135? at the maximum ambient temperature of 60
°
C).