![Yamatake 900 Series Скачать руководство пользователя страница 169](http://html.mh-extra.com/html/yamatake/900-series/900-series_user-manual_905236169.webp)
Yamatake Corporation
ST3000 Smart Transmitter Series 900 Electronic Differential Pressure/Pressure Transmitter
6-23
6-7 : Display and Change Transmitter Setting
6-7-1 :Overview
Applicable setting
The following settings (values and states) can be displayed or changed by operating
SFC keys. This operation can be executed even during measurements.
The following settings (values and states) can be displayed or changed by operating
SFC keys. This operation can be executed even during measurements.
a
: Enabled
-: Disabled
Save settings
After changing settings (values and states), save settings using this procedure.
Remarks:
Settings (values and states) that are input to the transmitter are automatically saved
after about 30 seconds. They are not erased by switching OFF the transmitter.
Item
Change
Display
Tag No.
a
a
Output format
a
a
Display format
a
a
High and low limits of engineering quantity
a
a
Low limit of set range
a
a
High limit of set range
a
a
Span of set range
a
a
Engineering unit
a
a
Damping-Time constant
a
a
Low flow cutoff value
a
a
Burnout direction
-
a
PROM No.
-
a
Software version
-
a
Sensor temperature
-
a
Step
Description
SFC screen
1
Press the
and
keys, in that order.
• The data has been saved in the transmit-
ter.
SHIFT
ENTER
( Yes )
NON-VOL
SHIFT-
DSTJ FIT-1234
WORKING...
DSTJ FIT-1234
DATA NONVOLATILE