6-35
6-7-7 :Display or Change Low Flow Cutoff Value
This function is effective only when Square Root is selected for the output format.
When the flow rate falls below a fixed value (valid range of low flow cutoff value:
0~20%), the flow rate is processed as zero.
Also, a dropout format (linear/zero) and a flow rate mode (DEFAULT/EXPAND) can
be selected.
Figure 6-2 Relationship Between Input and Output (%) Determined by Low Flow
Cutoff Value Setting
~Note
Flow rate mode
DEFAULT :
Ordinarily, this mode is selected, in most cases.
EXPAND :
This mode is selected when the range is expanded. For
example, when the range is set near the normal flow rate, or when
reverse flow rate output must be obtained using a reversible orifice.
7.1%
Linear
Square root
(Cutoff value+ Default value)
Square root
(Cutoff value+ Any set value)
Drop out linear
Drop out zero
Output
Output
Input
Input
Output
Input
Output
Input
Cutoff value