Ⅳ . SETTING OF PRESSURE

1. Switch contact confi guration

・  Composition  of  contact  of  this  instrument  is  as  shown  on 

the right.

・  If  the  instrument  is  not  applied  by  differential  pressure  we 

call such “

normal condition

” .

・  At  normal  condition,  the  contact  between  COM.  and  N.C. 

is closed, and between COM. and N.O. is open.

・  With  increase  of  differential  pressure  and  reaching  the  actuation  pressure,  the  contact  will  be  changed 

over ; between COM. and  N.C. is opened and between COM. and N.O. is closed.

2. Setting of upper limit/ lower limit

・  When  differential  pressure  applied  to  the  instrument  is 

increased  starting  from  zero  and  changes  over  the  electric 
contact from N.C. (normal close) to N.O. (normal open), the 
pressure at this moment is called “

actuation pressure

” .

・  When this differential pressure decreases from the pressure 

higher  than  this  actuation  pressure  activating  electrical 
contact and returning the contact from N.O. (normal open) 
to N.C. (normal close), the pressure at this moment is called 

reset pressure

” .

・  There is certain difference between actuation pressure and reset pressure and this is called “

dead band

” .

・  There are two types of the instrument. One is called “

upper limit setting type

” type (H) whose scale of 

setting knob is adjusted on actuation pressure,  the other is called “

lower limit setting type

” type (L) 

which is adjusted on reset pressure.

・  Be  careful  about  the  difference  between  the  upper  and  lower  limit  setting  switched  and  also  understand 

the relation between the pressure increase/ decrease and the contact composition before designing the 
operational sequence.

Depending  on  the  purpose  of  use,  choose  the  instrument 
either 

“upper limit setting type”

or

 “lower limit setting type”

Difference of contact movement between
“upper  limit  setting  type”  and  “lower  limit 
setting type”

In case of 1-6 kPa range with set value 2 kPa. 
(dead band is 0.6 kPa)

Adjusting of scale

Name plate

Upper limit 

setting type

Adjusted in 

activating pressure

In case of “upper limit setting type”

When the differential pressure increases, the 
circuit  is  closed  between  N.O.  and  COM.  at 
2 kPa.
Then  as  the  differential  pressure  decreases, 
the  circuit  is  opened  between  N.O.  and 
COM. at 1.4 kPa.

Lower limit 

setting type

Adjusted in 

reset pressure

In case of “lower limit setting type”

When the differential pressure increases, the 
circuit  is  closed  between  N.O.  and  COM.  at 
2.6 kPa.
Then  as  the  differential  pressure  decreases, 
the  circuit  is  opened  between  N.O.  and 
COM. at 2 kPa.

The scale of the setting knob is adjusted for both upper and lower limit setting type at our factory before 
shipping. It is not allowed for customers to convert from the upper limit setting to the lower limit setting or 
vice versa.

ᵢᶇᶄᶄᶃᶐᶃᶌᶒᶇᵿᶊᴾᶎᶐᶃᶑᶑᶓᶐᶃ

ᵟᶁᶒᶓᵿᶒᶇᶍᶌᴾᶎᶐᶃᶑᶑᶓᶐᶃ

ᵰᶃᶑᶃᶒᴾᶎᶐᶃᶑᶑᶓᶐᶃ

ᵱᶕᶇᶒᶁᶆᶇᶌᶅᴾᶂᶇᶄᶄᶃᶐᶃᶌᶁᶃ
ᵆᶂᶃᵿᶂᴾᶀᵿᶌᶂᵇ

ᵲᶇᶋᶃ

㻱㼤㼜㼘㼍㼚㼍㼠㼕㼛㼚㻌㼐㼕㼍㼓㼞㼍㼙㻌㼛㼒

㼟㼣㼕㼠㼏㼔㼕㼚㼓㻌㼐㼕㼒㼒㼑㼞㼑㼚㼏㼑㻌㼜㼞㼑㼟㼟㼡㼞㼑

ᾝᵌᾒᵌ

ᾒᾞᾜᵌ

ᾝᵌᾞᵌ

ᵧᶌᶁᶐᶃᵿᶑᶃᴾᶍᶄ
ᶂᶇᶄᶄᶃᶐᶃᶌᶒᶇᵿᶊ
ᶎᶐᶃᶑᶑᶓᶐᶃ

Содержание MS65F

Страница 1: ...I N S T R U C T I O N M A N U A L 653 0031 1 Nishi shiriike cho Nagata ku Kobe Japan TEL 078 631 6000 FAX 078 631 6020 READ THE INSTRUCTION MANUAL RoHS Compliant...

Страница 2: ...Caution of piping 6 7 Installation position 6 SETTING OF PRESSURE 1 Switch contact con guration 7 2 Setting of upper limit lower limit 7 3 Reset time 8 ABOUT BUILT IN MICRO SWITCH 1 Material of conta...

Страница 3: ...instrument The instrument is measurable for air and non corrosive gas only The machine is exclusive use of dry air 90 RH or less Using measuring the water or oil it may be damaged and causes the accid...

Страница 4: ...ce pressures Materials of pressure receiving element Pa kPa 60D 10 60 0 01 0 06 2 0 Pa 15 0 Pa Polyester lm 120D 20 120 0 02 0 12 4 0 Pa 20 0 Pa 300D 50 300 0 05 0 3 8 0 Pa 40 0 Pa 600D 100 600 0 1 0...

Страница 5: ...de 10 10 to 50 Hz Acceleration 39 m s2 each two hours on triaxial directions 100 m s2 each six times on triaxial direction Between each terminal and case 20 M or more 500 V DC megger Between each term...

Страница 6: ...trical load type The general electrical load type is decreased contact reliability refer to p 8 The withstanding pressure of the pressure receiving element means The max pressure under which the diaph...

Страница 7: ...nt of negative pressure Connect the tube to the low pressure side piping connector blue or L The high pressure port red or H should be opened to atmosphere but do not remove the piping connector c Mea...

Страница 8: ...it once in a while After the cleaning of the tank check that the air tightness is fully kept c Measurement of high temperature gases In the pressure measurement of high temperature gas use the pressur...

Страница 9: ...pressure the other is called lower limit setting type type L which is adjusted on reset pressure Be careful about the difference between the upper and lower limit setting switched and also understand...

Страница 10: ...contact for low electrical load cross point contact Magni ed drowing of contact for general load small rivet contact point 2 Contact material and applicable mecanism for low voltage and low current c...

Страница 11: ...ive force of inductive load by diode and avoid to apply high voltage to inbetween the contacts This method makes the return time of inductive load slower Choose the diode rated current is more than lo...

Страница 12: ...acid and it may also cause electrical contact failure or malfunction of switches b Silicone gas If the gas to be measured contains silicon produced from silicon contained in oil grease filling agent...

Страница 13: ...ain to x Replacement of air lter In case of using model with air lter MS65F depending on amount of work conduct disassembly and clean out once in 2 years periodically and replace lters and packings wi...

Страница 14: ...rument life For vinyl or plastic tube For metal tube Product code FG VT6 S Product code FG MT6 S T joint For vinyl or plastic tube Product code TVT6 4 6 For branching different I D 6 and 4 Product cod...

Страница 15: ...og speci cations or manual Handling or usage of the product other than as described in our product catalog speci cations or manual 2 Breakdown due to a reason other than a fault within our product 3 A...

Отзывы: