background image

RS-1600/1602-FC-SBD  User Guide

42

3.2.1 Power Supply/Cooling Module LEDs

The Power Supply/Cooling module incorporates 4 LEDs, located below the On/Off switch and shown in 

Table 3–1

.

• Under Normal conditions the LEDs should all be illuminated constant GREEN
• If a problem is detected the color of the relevant LED will change to AMBER.

3.3 Ops Panel LEDs

The Ops Panel LEDs status conditions are defined in 

Table 3–2

 and the LEDs are illustrated in 

Figure 3–1

.

Table 3–1

PSU LEDs

 AC PSU

-48V DC PSU

PSU Good

Green

PSU Good

Green

AC input Fail

Amber

Battery Fail

Amber

 Fan Fault

Amber

Fan Fault

Amber

DC Output Fail

Amber

DC Output Fail

Amber

Figure 3–1

Ops Panel LEDs and Switches

Содержание RS-1600-FC-SBD

Страница 1: ...RS 1600 FC SBD and RS 1602 FC SBD Installation and User Guide Part No 46329 01A Issue 1 0 12 January 2004...

Страница 2: ...no liability for any errors that may arise No part of this document may be transmitted or copied in any form or by any means for any purpose without the written permission of the Authors Acknowledgmen...

Страница 3: ...er Option 3 1 3 The Plug in Modules 4 1 3 1 Power Supply Cooling Module 4 1 3 2 Operators Panel 6 1 3 3 SBD Input Output Module 7 1 3 4 Drive Carrier Module 11 1 3 5 Dummy Carrier Modules 12 1 3 6 Bla...

Страница 4: ...closures 31 2 8 Drive Enclosure Device Addressing 34 2 8 1 Drive Start 35 2 9 Drive Carrier Configuration 36 2 9 1 Planning and Configuring Your Installation 36 2 10 Drive Carrier Installation 36 2 10...

Страница 5: ...2 Power Supply Cooling Faults 51 4 5 3 Thermal Control 52 4 5 4 Thermal Alarm 53 4 5 5 Thermal Warnings 54 4 6 Dealing with Hardware Faults 54 4 7 Continuous Operation During Replacement 54 4 8 Replac...

Страница 6: ...vi RS 1600 1602 FC SBD User Guide...

Страница 7: ...pursuant to Part 15 of the FCC rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment...

Страница 8: ...0 FC SBD or RS 1602 FC SBD enclosure can weigh up to 37kg 81lb Do not try to lift it by yourself Chassis Warning Label Weight Hazard Do not lift RS 1600 FC SBD or RS 1602 FC SBD populated enclosures b...

Страница 9: ...r Hazards The power connection should always be disconnected prior to removal of the Power Supply Cooling module from the enclosure A safe electrical earth connection must be provided to the power cor...

Страница 10: ...quipment is intended to operate from a centralized dc supply system with a NOMINAL voltage of 48V DC or 60V DC The voltage from a nominal 48V DC system may vary due to float charging or discharge cond...

Страница 11: ...ranch Protector current rating of wire supplying the equipment U S National Electric Code Article 210 3 Article 240 Rack System Precautions The following safety requirements must be considered when th...

Страница 12: ...ive modules Disk units are fragile Handle them with care and keep them away from strong magnetic fields All the supplied plug in modules and blanking plates must be in place for the air to flow correc...

Страница 13: ...cumentation RS 1600 FC SBD and RS 1602 FC SBD Quick Installation Guide P N 46328 01 RS Salient Series Rack Installation Guide P N 43638 02 Revision History Version Date Description of Change 1 0 Janua...

Страница 14: ...RS 1600 1602 FC SBD User Guide xiv...

Страница 15: ...Introduction 1 Chapter 1 Introduction 1 1 RS 1600 FC SBD and RS 1602 FC SBD Subsystems Figure 1 1 Typical Storage Subsystem Enclosure...

Страница 16: ...cuit board PCB and module runner system This chassis assembly also includes an integral Operators Ops Panel mounted at the rear The RS 1602 series chassis is longer than the RS 1600 series chassis to...

Страница 17: ...tion 3 1 2 2 Tower Option An optional tower kit is available which can be fitted to the rack chassis described here Figure 1 2 Enclosure Chassis Front Figure 1 3 Enclosure Chassis Rear Figure 1 4 Towe...

Страница 18: ...t completely empty 1 3 1 Power Supply Cooling Module Two variants of the Power Supply Cooling module are available for the RS 1600 FC SBD and RS 1602 FC SBD subsystems Auto ranging AC 450W Power Suppl...

Страница 19: ...ator removable part It should only be removed by a technician who has knowledge of the hazards present within the module 1 3 1 3 Multiple Power Supply Cooling Modules The RS 1600 FC SBD or RS 1602 FC...

Страница 20: ...er which is used to monitor and control all elements of the Enclosure 1 3 2 1 Ops Panel Indicators and Switches The Ops Panel includes Light Emitting diodes LEDs which show the status for all modules...

Страница 21: ...within the SBD modules At any host port this appears as one FC AL logical loop The SBD module internal processor monitors error conditions on each disk drive port and will automatically isolate devic...

Страница 22: ...module incorporates the following LED indicators Host LED Functions LED State Description Host Port 0 Signal Good Green incoming FC signal GOOD Host Port 1 Signal Good Green incoming FC signal GOOD Ho...

Страница 23: ...tion to an active host or insertion or removal of a drive will cause a LIP to occur This feature may be optionally disabled please contact your supplier for details If the multi port trunking feature...

Страница 24: ...ailable in 1Gb 2Gb JBOD or RAID variants for operation with Fibre Channel or Serial ATA drives by changing the LRC modules Please contact your supplier for details Figure 1 10 Enclosure with SBD Modul...

Страница 25: ...g of the drive backplane connector An anti tamper lock operated by a torx socket type key Two versions of the drive carrier Figure 1 12 are offered for installation in RS 1600 or RS 1602 chassis They...

Страница 26: ...ertures are filled before operating the unit Dummy Carriers and or Blank modules are available for this purpose 1 4 Visible and Audible Alarms The functional modules have associated status LEDs The Op...

Страница 27: ...m flange to maximum extremity of enclosure rear hold down RS 1600 RS 1602 20 12 20 55 511 551 Depth from flange to furthest extremity at front of unit 0 67 17 Tower Enclosure inches mm Height 19 72 50...

Страница 28: ...priate to the country and must have safety approvals acceptable in that country DC Input Voltage Range 40V to 60V DC Rated DC Line Inrush Current 50A peak Rated Current 17 A Safety Compliance UL 60950...

Страница 29: ...erational 30g 10ms 1 2 sine Vibration Operational 0 21grms 5 500 Hz Random Vibration Non Operational 1 04grms 2 200 Hz Random Vibration Relocation 0 3g 2 200 Hz sine Acoustics Sound Pressure Operating...

Страница 30: ...se contact your customer service representative SES Reporting Using vendor specific Extended Pages the following information can be gathered Bypass reason specific reason why the port is not inserted...

Страница 31: ...a copy of the SBD SES specification from your supplier LED Color Description Status Green OFF Flashing All device ports GOOD 2Gb s All device ports GOOD 1Gb s Drives bypassed on module SBD Module Faul...

Страница 32: ...RS 1600 1602 FC SBD User Guide 18...

Страница 33: ...ules are shown in Figure 2 1 Please refer to sections 2 6 2 5 for details of SBD module configurations and installation Caution Dummy Carriers and Blank Modules MUST be fitted to ALL unused bays there...

Страница 34: ...D subsystems are housed in a 4 x 4 enclosure i e 4 bays wide by 4 bays high The front bays are numbered 1 to 4 from left to right viewed from the front Bays are numbered from 1 top row to 4 bottom row...

Страница 35: ...mm from front flange to rear metalwork excludes rear cabling Weight up to 37kg dependent upon configuration per enclosure A minimum gap of 25mm 1inch clearance between the rack cover and front of dra...

Страница 36: ...ails until the front flanges engage on the rack Ensure the chassis is centrally located 3 If in doubt about correct orientation the drive bays at front should have their black drive connectors toward...

Страница 37: ...t must be inverted by squeezing together the two sides of the tab removing them from their mountings inverting and then replacing them as shown in Figure 2 3 1 Check for damage especially to the rear...

Страница 38: ...RS 1600 1602 FC SBD User Guide 24 Figure 2 4 AC Power Supply Cooling Module Handle in Open Position Figure 2 5 Installing an AC Power Supply Cooling Module 1...

Страница 39: ...0V DC to 60V DC The voltage from a nominal 60V DC system may vary due to float charging or discharge conditions from 48V DC to 72V DC Caution If this equipment is used in a manner not specified by the...

Страница 40: ...Wiring method must be code compliant in the field Wiring methods must be in accordance with the U S National Electric Code Article 300 Earthing This equipment is designed to permit the connection of t...

Страница 41: ...Terminal Block Connections The terminal block is suitable for Field Wiring and Factory Wiring 2 4 3 3 Installation Procedure Warning Installation of this Power Supply Cooling module should only be pe...

Страница 42: ...ice located near to the equipment 5 Remove the terminal block cover 6 Connect the wires in accordance with the Wiring Instructions in section 2 4 3 4 7 Replace the terminal block cover Figure 2 8 inst...

Страница 43: ...sion Connectors If fitted with Optical modules the modules must be a UL or other North American NRTL RECOGNISED COMPONENT and the laser in the module must comply with Laser Class 1 US 21 CFR J and EN...

Страница 44: ...FC SBD User Guide 30 4 Cam the module home by manually closing the latches see Figure 2 13 A click should be heard as the latch engages Figure 2 12 SBD Module Latch Operation Figure 2 13 Installing a...

Страница 45: ...red and mapped by the controller Each SBD module can be connected to up to 4 Host Bus adaptors as shown in Figure 2 14 Note There are no external terminators required with Fibre Channel architecture a...

Страница 46: ...each enclosure in a physical loop to a different range Drive bay 4 4 is set for immediate start all other bays are delayed spin start 12 seconds x Module 8 of the SEL_ID unless there are two active P...

Страница 47: ...Getting Started 33 Figure 2 15 Connecting Multiple Enclosures...

Страница 48: ...ch settings are as follows Notes 1 ON switch to the Left OFF switch to the Right 2 Switches 2 to 6 and 12 are Not Used 3 Modes 2 and 3 are Not Used Table 2 3 Ops Panel Switch Functions Default setting...

Страница 49: ...11 12 13 14 15 Mode 1 0 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 1 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 2 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 3 44 45 46 47 48 49 50 51 52 53 54 55 56...

Страница 50: ...illed with either a drive carrier or front dummy fascia no bays should be left completely empty 2 9 1 2 Drive Configuration Important After you have installed the drive carrier modules in your RS 1600...

Страница 51: ...se of the carrier will engage into a slot in the enclosure Continue to push firmly until the handle fully engages A click should be heard as the latch engages and holds the handle closed Figure 2 19 N...

Страница 52: ...1602 FC SBD User Guide 38 Note Removal is the reverse of this procedure press on the latch to release the handle Figure 2 18 Installing a Drive Carrier Module 2 Figure 2 19 Installing a Drive Carrier...

Страница 53: ...ck key provided into the cutout in the handle 2 Locate the key into its socket 3 Rotate the key in a clockwise direction until the indicator is visible in the aperture beside the key 4 Remove the key...

Страница 54: ...from the enclosure 2 12 Grounding Checks Perform these checks to ensure that a safe grounding system is provided If a rack distribution system is being used Ensure power is removed from the rack Conne...

Страница 55: ...ditions Follow the procedure below to Power On the enclosure 1 Apply AC power to the enclosure Turn the Power Supply modules to ON 2 On the Ops Panel the Audible Alarm beeps once all LEDs flash for 7...

Страница 56: ...ed constant GREEN If a problem is detected the color of the relevant LED will change to AMBER 3 3 Ops Panel LEDs The Ops Panel LEDs status conditions are defined in Table 3 2 and the LEDs are illustra...

Страница 57: ...orporates two indicators an upper GREEN and lower AMBER In normal operation the Green LED will be ON and will flicker as the drive operates The Amber LED will be OFF In normal operation It will only b...

Страница 58: ...RS 1600 1602 FC SBD User Guide 44...

Страница 59: ...d cooling conditions are housed within the Power Supply Cooling modules There is independent monitoring for each unit If a fault is indicated on the Ops Panel please refer to Table 4 2 4 1 1 Initial S...

Страница 60: ...resent check that the cable has not been inverted during installation 6 Check the SBD module setup as follows Check that the SBD module has been correctly installed and all external links and cables a...

Страница 61: ...all the modules The Ops Panel LEDs are shown in Figure 4 1 and defined in Table 4 2 For details on how to remove and replace a plug in module see Section 4 8 Note The Ops Panel is supplied as an integ...

Страница 62: ...ult On On Flash x x x Over or Under temperature On Off On x x x ESI LED on SBD ESI processor module A Failed On Off On x x x ESI LED on SBD ESI processor module B Failed On Off On x x x None Unknown i...

Страница 63: ...push button is located above the indicators on the Ops Panel see Figure 4 1 When the alarm is muted it will continue to sound with short intermittent bleeps to indicate that a problem still exists It...

Страница 64: ...e during power up 4 4 1 Dummy Carrier Modules Dummy Carrier modules must be fitted to all unused drive bays to maintain a balanced air flow 4 4 2 Auto Start Failure Unless otherwise selected at instal...

Страница 65: ...the problem persists then change the module 2 Check for other AMBER LED indications on the drives carriers If none are evident then there may either be an ESI processor problem or a Backplane problem...

Страница 66: ...mal control process is for the fans to automatically increase in speed when a thermal threshold is reached This may be caused by higher ambient temperatures in the local environment and may be perfect...

Страница 67: ...1 Check local ambient environment temperature is below the upper 40 C specification 2 Check the installation for any airflow restrictions at either the front or rear of the enclosure A minimum gap of...

Страница 68: ...ply units electronics modules and blank modules must be in place for the air to flow correctly around the cabinet 4 7 Continuous Operation During Replacement Depending on how the subsystem is set up i...

Страница 69: ...re should always be two power supply units installed you can continue working while replacing the faulty module 1 Make sure you identify the faulty Power Supply Cooling module correctly from the two m...

Страница 70: ...RS 1600 1602 FC SBD User Guide 56 Figure 4 3 Removing Inserting an AC Power Supply Cooling Module 1 Figure 4 4 Removing Inserting an AC Power Supply Cooling Module 2...

Страница 71: ...ollowing Removal procedures 1 Switch off power at the PSU switch 2 Remove all supply power by turning off the supply at the disconnect device located near to the equipment 3 Remove the terminal block...

Страница 72: ...RS 1600 1602 FC SBD User Guide 58 Figure 4 6 Removing Inserting a 48V DC Power Supply Cooling Module 1 Figure 4 7 Removing Inserting a 48V DC Power Supply Cooling Module 2...

Страница 73: ...maging the connector pins Do not install the module if any pins appear to be bent 2 With the PSU handle Figure 4 7 in the open position slide the module into the enclosure Important install the Power...

Страница 74: ...rning The 48V and 48V terminals are not connected to chassis earth 1 For installations with 48V earthed a shorting link must be added see Figure 4 9 2 For installations with a separate earth connect t...

Страница 75: ...nless a replacement can be immediately added The system must not be run without all units in place 1 Using two hands grasp each latch between the thumb and forefinger of each hand Squeeze thumb and fo...

Страница 76: ...e open position slide the SBD module into the enclosure until the latch engages automatically 2 Cam the module home by manually closing the latches see Figure 4 13 3 A click should be heard as the lat...

Страница 77: ...must be off 2 Gently withdraw the Drive Carrier Module approximately 1 inch 25mm and wait 30 seconds 3 Withdraw the module from the drive bay and fit a replacement module in accordance with the instru...

Страница 78: ...RS 1600 1602 FC SBD User Guide 64...

Страница 79: ...transmission of data signals between computer equipment Note Cable is UK preferred terminology for either a power cord or a data cable Character A representation coded in binary digits of a letter nu...

Страница 80: ...S 1600 FC SBD or RS 1602 FC SBD enclosure can contain sixteen drive modules two power supply cooling modules and two SBD I O modules Operating system The software running the host computer For example...

Страница 81: ...4 12 19 21 52 54 enclosure bay numbering convention 20 enclosure expansion 31 Enclosure Services Processor 45 Enclosure System Interface Operators Panel 6 ESD 21 55 ESD precautions 63 ESI processor 51...

Страница 82: ...e 2 7 9 19 29 31 46 49 51 61 62 SBD module LEDs 49 SBOD 2 SEL_ID Address Range selector switch 6 SEL_ID base address 34 Select ID 46 SES 36 SES drives 35 SFP 9 31 starting drives 43 SYSTEM LED 50 51 t...

Отзывы: