RS-1600/1602-FC-SBD User Guide
14
1.5.4 -48V DC Power (450W PSU)
1.5.5 PSU Safety and EMC Compliance
1.5.6 Power Cords
1
United States
Must be NRTL LISTED (National Recognized Test Laboratory, e.g. UL)
2
Europe & Others
General requirements:-
Important
The Plug and the complete power cord assembly must meet the standards appropriate to the
country, and must have safety approvals acceptable in that country.
DC Input Voltage Range
-40V to -60V DC Rated
DC Line Inrush Current
50A peak
Rated Current
17 A
Safety Compliance
UL 60950
IEC 60950
EN 60950
EMC Compliance
CFR47 Part 15B Class A
EN55022
EN55024
Cord type
SV or SVT, 18 AWG minimum, 3 conductor, 4.5 M max length.
Plug
NEMA 5-15P grounding-type attachment plug rated 120V 10A;
or
IEC 320 C14, 250V, 10A.
Socket
IEC 320, C-13, 250V, 10A.
Cord type
Harmonized, H05-VVF-3G1.0
Socket
IEC 320, C-13, 250V, 10A.