Heat / Cooling meter integrator PolluTherm 

Installation and operational instructions 

 

 
M H 6111 INT PolluTherm, page 4 

flush the pipe system thoroughly. Then close the 
shut-off valves, remove the fitting piece, clean the 
sealing surfaces and install the flow sensor using 
new gaskets. Take care to not reduce the pipe 
diameter by bad positioning of the gaskets, 
particularly if flanged versions are installed.  

 
5.2 Installation of the temperature sensors 

 
PolluTherm operates with separately approved 
and paired temperature sensors type Pt 500. The 
applicable type is specified on the front of the 
integrator. 
 
We recommend the use of the MID starter kit 
consisting of special ball valves with temperature 
sensor entries M 10 x 1 with integrated union nuts 
and one spool piece (see manual MH 1131 INT). 
This starter kit is compatible with temperature 
sensor types L = 45 mm / D = 5,2 and DS 27,5. It 
is available up to R1 ½ ” (DN 40). 
 
When using Sensus temperature sensors, length 
100 and 150mm the sensitive zone is ca. 10 to 15 
mm measured from the temperature sensor’s tip 
and has to be positioned as close as possible to 
the 

middle of the pipe diameter

. Refer to the 

following guide for installing such temperature 
sensors: 
 
Nominal sizes < DN 50*: Install the temperature 
sensors in an angle of 45° 

towards 

the flow 

direction (see figure 4).  
 
 
Nominal sizes > DN 100*: Install the temperature 
sensors vertically to the flow direction (see figure 
5). 
 
For DN 65 and DN 80 both installation positions 
are valid 

 

For larger nominal sizes (e.g. DN 150) the 
immersion sleeve has to be immersed at least as 
deep as 50 mm into the pipe. 

 

 

Fig. 4: Example diagram for nominal size DN 50 

* < DN 50 installation in a pipe elbow is also possible 
 

 

Fig. 5: Example diagram for nominal size DN 100 

* For DN 65 and DN 80 both installation positions are possible

 

5.3 Mounting of the integrator  

 
Fasten the enclosed C-rail with two screws in a 
horizontal position at the chosen place. Attach the 
housing to the C-rail and lift the red snap hook 
using a flat slot screw driver.  
Press the body onto the C-rail and release the 
snap hook.  
For removal lift the red snap hook with a flat slot 
screw driver and take the housing off. 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 6: Back of the housing with mounted C-rail 

 
6. Connection of the sub-units 

 
To open the housing press the two locking caps at 
the two lower angles of the housing lid and turn 
the lid upwards. 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 7: Open terminal block, one of the 

preshaped rubber parts removed 

 

Содержание SENSUS PolluTherm Integrator

Страница 1: ...t into the heat meter 11 11 8 Combined heating cooling meter ordering option 11 11 9 Optional integrated data logger ordering option 12 11 10 Retrofitting from battery unit to power supply unit 12 12...

Страница 2: ...tection Only specially trained and authorized personnel are permitted to carry out the connection Moreover attention is to be paid to the national technical rules Voltage 220 240 V AC or 24 V AC Frequ...

Страница 3: ...g systems It is recommended to install the flow sensor in the warmer line return pipe of the cooling device PolluTherm X installation in warmer line has to be used Please note the approved minimum tem...

Страница 4: ...of the pipe diameter Refer to the following guide for installing such temperature sensors Nominal sizes DN 50 Install the temperature sensors in an angle of 45 towards the flow direction see figure 4...

Страница 5: ...8 Four wire connection 7 8 und 3 4 Screening if any Start by removing the appropriate preshaped rubber part from the integrator housing see figure 7 Then pull the cable through the hole in the presha...

Страница 6: ...ntervals of 4 seconds and shows the accumulated heat energy By a push on the red key the first display item in the user menu accumulated heat energy is activated The other five menus can be obtained b...

Страница 7: ...es on an adjustable annual target Target day value for heat and cooling energy resp Target day value for volume Target day value for tariff 1 if activated Target day value for tariff cold if activated...

Страница 8: ...play shows a month selectionor wait for five minutes 8 4 Service menu example Each display item is marked with a man symbol The service menu shows maximum values and meter settings Absolute maximum fl...

Страница 9: ...t three digits of the eight digit serial number on the meter housing At the beginning 000 appears Push the key for approx 2 seconds the zero on the left side starts flashing By continuously pushing th...

Страница 10: ...ow temperature sensors In most cases the error situation Err 1010 is caused by temporary system conditions where the temperature in the warmer line drops by at least 3K below the temperature in the co...

Страница 11: ...r reading 0 00 m The activation of the inputs has to be done via the service software MiniCom menu item set pulse input parameters The meter IDs of the pulse meters have to be set there as well as the...

Страница 12: ...only the screw on the right side under the KK1 seal user seal of the plastic cover Pull the integrated module forward from the connection The seals in the middle and on the left side may not be remove...

Страница 13: ...the lower 3 and 4 the electric resistance of the extension cable or cables does do not influence the measurement and the reading of the temperatures Material number 28505033 Edition 007 August 2019 Su...

Страница 14: ...Heat Cooling meter integrator PolluTherm Installation and operational instructions M H 6111 INT PolluTherm page 14 Annex 1 Declaration of conformity acc directive 2004 22EC MID...

Отзывы: